![Fujitsu AUXG30KRLB Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/fujitsu/auxg30krlb/auxg30krlb_service-instruction_2343789050.webp)
Detective Actuators:
Wired remote controller ( 2-Wire )
Indoor unit Controller PCB circuit
Detective details:
When the address number set by auto setting and manual setting are
mixed in one RC group.
When the duplicated address number exists in one RC group.
Check Point 3 : Check Indoor unit controller PCB
Forecast of Cause :
1. Wrong wiring of RCgroup 2. Wrong remote address setting 3. Indoor unit controller PCB failure
4. Remote controller failure
Check Point 1 : Wire installation
Wrong wire connection in RCgroup (Please refer to the installation manual)
Change controller PCB and check the Error after setting remote controller address
Check if controller PCB damage
Check Point 2 : Wrong RCgroup setting
The given address number by auto setting (00) and the manual set number (Except 00)
were not existing in one RCG.
The remote controller address setting by U.I. were not existing same address.
The duplicated address number is not existing in one RCgroup
Trouble shooting 7
INDOOR UNIT Error Method:
Indoor unit address setting error
Indicate or Display:
Error code : 26
02-08
OK
OK
Outdoor unit :
n: n times blinking
: Light ON
: Light OFF
Mode Error L1 L2
L6
L5
L4
L3
2
5
15
Содержание AUXG30KRLB
Страница 2: ...1 CONTROL AND FUNCTIONS 2020 06 01 SR_CH04_AU006EF_01 ...
Страница 4: ...8 8 High temperature and high pressure release control 04 36 CONTENTS continued ...
Страница 5: ......
Страница 42: ...2 TROUBLE SHOOTING CASSETTE type INVERTER ...
Страница 90: ...Jun 2020 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...