10.VARIOUS PROTECTIONS
01-23
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
(Discharge release)
Discharge gas temperature sensor (discharge thermistor : outdoor side)
will detect discharge gas temperature.
When discharge temperature becomes higher than 104°C,
compressor frequency is decreased 20rps,
and it continues to decrease the frequency for 20rps every 120 seconds
until temperature becomes lower than 101°C.
When discharge temperature becomes lower than 101°C,
control of compressor frequency is released.
When discharge temperature becomes higher than 110°C,
compressor is stopped and the indoor unit LED starts blinking.