4. DRY OPERATION
In dry operation, maximum compressor frequency is defined
by set temperature, and room temperature as below.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
Maximum compressor frequency is defined by zone.
Zone is defined by set temperature and room temperature.
20 rps
16 rps
0 rps
AOYG09KMCBN
X zone
J zone
Y zone
22 rps
18 rps
0 rps
AOYG12KMCBN
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts = Set temperature
26 rps
18 rps
0 rps
AOYG14KMCBN