Troubleshooting 19
OUTDOOR UNIT Error Method:
Discharge temperature error
02-23
Cooling operation
OK
OK
OK
OK
OK
Heating operation
Outdoor unit Main PCB
Discharge temperature thermistor
"Protection stop by "discharge temperature 110degC during compressor
operation"" generated 2 times within 24 hours.
Check Point 1 : Check if 3-way valve is open.
Discharger thermistor characteristics check.
(Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor,
refer to the "Trouble shooting 11".
Check Point 4 : Check the discharge thermistor
EEV open?
Strainer clogging check (before and after EEV)
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check (PARTS INFORMATION 5)
Check Point 2 : Check the EEV, strainer
Check Point 5 : Check the refrigerant amount
Leak check
EEV open?
Strainer clogging check (before and after EEV)
Check Point 2 : Check the EEV, strainer
If the 3-way valve was closed, open the 3-way valve
and check operation.
Check Point 1 : Check if 2-way valve is open.
If the 2-way valve was closed, open the 2-way valve
and check operation.
OK
Detective actuators:
Detective details:
Forecast of cause :
Refer to "Service Parts Information 3".
Refer to "Service Parts Information 3".
1. 2,3-way valve not opened
2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Discharge temperature thermistor
failure
5. Insufficient refrigerant
6. Main PCB failure