4. AUTO CHANGEOVER OPERATION
01-03
Operation flow chart
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1°C steps.
START
Room temp.
>
Ts+2
°C
?
COOLING (AUTO:DRY)
OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
T
S
:
Setting temperature
Room temp.
<
Ts -2
°C
?
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
Middle zone
YES
NO
YES
Outdoor temperature
<
25
°C?
NO
YES
YES
NO
YES