2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 6°C than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is higher 1°C than a set temperature, the compressor will be
stopped.
* When the room temperature is b1°C to -6°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
( Table2 : Compressor Frequency Range )
01-02
minimum
frequency
maximum
frequency
AOTG18KMTC
AOTG22KMTC
AOTG24KMTC
10rps
10rps
10rps
130rps
130rps
130rps
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table3.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
( Table3 : Compressor frequency )
( Fig.2 : Compressor Control based on Room Temperature )
Operating
frequency
J zone
Y zone
X zone
24rps
18rps
0rps
18KMTC
22KMTC
24KMTC
X zone
J zone
Y zone
Room
temperature drops
Room
temperature rises