OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 1 time Flash, Timer lamp: 1 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 11]
YES
YES
NO
3
L
N
RED
WHITE
BLACK
+
-
OK
1. Connection failure 2. External cause 3. Main PCB failure 4. Outdoor unit fan motor failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check Point 2 : Check Connection
Check any loose or removed connection line of
Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198V (AC220V -10%) - 264V (10%) appears
at Outdoor Unit Terminal L - N.
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC90V and AC270V at Outdoor Unit Terminal L - 3.
>> If it is abnormal, Check Outdoor unit fan motor (PARTS INFORMATION 5)
>> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB.
>> If Outdoor fan motor is normal, replace Main PCB.
When the indoor unit cannot receive the serial signal from Outdoor unit
more than 2minutes after power ON, or the indoor unit cannot receive
the serial signal more than 15seconds during normal operation.
2-2 TROUBLE SHOOTING WITH ERROR CODE
Serial communication error
(Serial Reverse Transfer Error)
Outdoor unit Main PCB
Outdoor unit fan motor
02-10
Содержание AOTG18KMTC
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 25: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Страница 82: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 89: ...Jan 2019 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...