0.1
sec.
blinki
ng
0.5 sec
2 times
Room temperature
thermistor defective
The room temperature thermistor detected a abnormal temperature when the power was turned on.
> Remote control does not operate.
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective.
0.5 sec
2 times
0.1 sec.
blinking
Indoor Unit
Thermistor
Error
0.1
sec.
blinki
ng
0.5 sec
3 times
Indoor Heat Exchanger
Thermistor Error
The detection value of the indoor heat exchanger thermistor is either open or shorted when the power is ON.
> Remote control does not operate.
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective.
0.1
sec.
blinki
ng
0.5 sec
2 times
Discharge Thermistor
Error
The detection value of the discharge thermistor is either open or shorted
> Compressor, Outdoor Fan : OFF (It automatically releases when the normal value is detected.)
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective.
0.1
sec.
blinki
ng
0.5 sec
3 times
Outdoor Heat Exchanger
Thermistor Error
The detection value of the outdoor heat exchanger thermistor is open.
> Compressor, Outdoor Fan : OFF (It automatically releases when the normal value is detected.)
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective
0.5 sec
3 times
0.1 sec.
blinking
Outdoor Unit
Thermistor
Error
0.1
sec.
blinki
ng
0.5 sec
4 times
Outdoor Temperature
Thermistor Error
The detection value of the outdoor temperature thermistor is either open or shorted
> Compressor, Outdoor Fan : OFF (It automatically releases when the normal value is detected.)
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective.
0.5 sec
4 times
0.1 sec.
blinking
Indoor Unit
Controller
Error
0.1
sec.
blinki
ng
0.5 sec
2 times
Forced Auto Switch
Error
Forced Auto Switch becomes ON for 10 consecutive seconds.
> It indicates the error but the operation continues.
[Diagnosis Point]
- Check if Forced Auto Switch is kept pressed.
- Forced Auto Switch defective.
- Controller PCB defective.
07
-0
4
Содержание AO*12LFBC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...D I M E N S I O N S AS 12LSBCW AO 12LFBC Models AS 9LSBCW AO 9LFBC unit mm 275 2 000 215 790 02 02 ...
Страница 12: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 16: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 20: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 40: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 46: ......
Страница 47: ......
Страница 70: ...9 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 83: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS17032005 March 2005 Printed in Japan ...