Self - diagnosis function and Checking points
Large Division Error
Indication
Small Division Error
Indication
Operation
Timer
Large Div.
Contents
Opera
tion
Timer
Small Div. Contents
(Protection)
Diagnosis Method
0.1
sec.
blinki
ng
0.5 sec
2 times
Serial reverse transfer
error at starting up
operation
At the start up, the indoor unit does not receive the signal for 10 consecutive seconds from the time when the
power relay was ON. > Permanent stop after 30 seconds.
[Diagnosis Point]
-
Check the indoor/outdoor cable connection (in order). If the cable wiring is not abnormal, measure the
voltage of the outdoor unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis
method.)
0.1
sec.
blinki
ng
0.5 sec
3 times
Serial reverse transfer
error during the
operation
When the indoor unit does not receive the signal for 10 consecutive seconds during the operation > Permanent
stop after 30 seconds.
[Diagnosis Point]
- Check the indoor/outdoor cable connection (in order). If the cable wiring is not abnormal, measure the
voltage of the outdoor unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis
method.)
0.1
sec.
blinki
ng
0.5 sec
4 times
Serial forward transfer
error at starting up
operation
The outdoor unit does not receive the signal for 10 consecutive seconds from the time when the power relay was
ON. > Outdoor unit stops.
[Diagnosis Point]
- Check the indoor/outdoor cable connection (in order). If the cable wiring is not abnormal, measure the
voltage of the outdoor unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis
method.)
ON
1 sec.
blinking
Transmission
Error
0.1
sec.
blinki
ng
0.5 sec
5 times
Serial forward transfer
error during the
operation
When the outdoor unit does not receive the signal for 10 consecutive seconds during the operation >
Outdoor unit stops.
[Diagnosis Point]
- Check the indoor/outdoor cable connection (in order). If the cable wiring is not abnormal, measure the
voltage of the outdoor unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis
method.)
07
-0
3
Содержание AO*12LFBC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...D I M E N S I O N S AS 12LSBCW AO 12LFBC Models AS 9LSBCW AO 9LFBC unit mm 275 2 000 215 790 02 02 ...
Страница 12: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 16: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 20: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 40: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 46: ......
Страница 47: ......
Страница 70: ...9 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 83: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS17032005 March 2005 Printed in Japan ...