3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table 3. However, after the compressor is driven, the indoor unit shall
run at operation frequency of 58Hz, for a minute.
Operating
frequency
AS*9LSACW
33Hz
AS*12LSACW
33Hz
AS*9LSBCW
33Hz
AS*12LSBCW
33Hz
AS*14LSBCW
24Hz
AS*18LSBCW
24Hz
room room
temperatu re temperature
compressor ON
Ts+1.5 C
Ts+0.5 C
compressor OFF
Compressor
ON
OFF
Indoor fan
Dry air flow
S
-
Lo
OFF
10 30 60 180 60 180 60 10 30 (sec)
( Table 3 : Compressor frequency )
( Fig.3 : Compressor Control based on Room Temperature )
( Fig.4 : Indoor Fan Control )
05-03
Содержание AO*12LFBC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...D I M E N S I O N S AS 12LSBCW AO 12LFBC Models AS 9LSBCW AO 9LFBC unit mm 275 2 000 215 790 02 02 ...
Страница 12: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 16: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 20: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 40: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 46: ......
Страница 47: ......
Страница 70: ...9 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 83: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS17032005 March 2005 Printed in Japan ...