12. Safety devices
Type of protection
Protection form
Model
AOU24RLXFZ
Circuit protection
Current fuse
(Main PCB)
250 V, 5 A
250 V, 3.15 A
Current fuse
(Near the terminal)
250 V, 10 A
Fan motor protection
Temperature thermistor
Activate
302 ±27 °F
(150 ±15 °C)
Fan motor stop
Reset
248 ±27 °F
(120 ±15 °C)
Fan motor restart
Compressor protection
Temperature thermistor
Activate
230 ±4 °F
(110 ±2 °C)
Compressor stop
Reset
176 ±4 °F
(80 ±2 °C)
Compressor restart
Thermal protection program
(Outdoor temp.)*
Activate
-15 °C
Compressor stop
Reset
—
Refrigerant circuit
protection
Pressure switch 1
Activate
609 ±15 PSI
(4.2 ±0.1 MPa)
Reset
464 ±22 PSI
(3.2 ±0.15 MPa)
Pressure switch 2: For control device. (Refer to the wiring diagram.)
*: Only for cooling or dry operation.
- 244 -
12. Safety devices
OUTDOOR UNIT
AOU24RLXFZ
OUTDOOR UNIT
AOU24RLXFZ