6. Capacity table
6-1. Combinations
¢
Model: AOU24RLXFZ
Cooling
1) Non-ducted
Combination of indoor unit
Rated capacity for each indoor
unit (kBtu/h)
Maximum capacity for each in-
door unit (kBtu/h)
Total capacity
(kBtu/h)
Input power (kW)
Room 1
Room 2
Room 3
Total
Room 1
Room 2
Room 3
Room 1
Room 2
Room 3
Min.
Rated
Max.
Min.
Rated
Max.
7
7
-
14
7.05
7.05
-
8.70
8.70
-
6.10
14.10
17.40
0.50
1.20
1.51
7
9
-
16
7.09
9.11
-
8.66
11.14
-
6.10
16.20
19.80
0.50
1.36
1.78
7
12
-
19
7.07
12.13
-
8.33
14.27
-
6.10
19.20
22.60
0.50
1.63
2.20
7
15
-
22
6.87
13.73
-
8.05
16.10
-
6.10
20.60
24.15
0.50
1.70
2.54
7
18
-
25
6.16
15.84
-
7.20
18.50
-
6.10
22.00
25.70
0.50
1.76
2.87
9
9
-
18
9.00
9.00
-
10.75
10.75
-
6.10
18.00
21.50
0.50
1.55
2.02
9
12
-
21
9.00
12.00
-
10.11
13.49
-
6.10
21.00
23.60
0.50
1.73
2.45
9
15
-
24
8.41
13.09
-
9.70
15.10
-
6.10
21.50
24.80
0.50
1.75
2.66
9
18
-
27
7.33
14.67
-
8.67
17.33
-
6.10
22.00
26.00
0.50
1.76
2.87
12
12
-
24
11.00
11.00
-
12.50
12.50
-
6.10
22.00
25.00
0.50
1.74
2.74
12
15
-
27
10.15
11.85
-
12.46
14.54
-
6.10
22.00
27.00
0.50
1.75
2.87
7
7
7
21
7.00
7.00
7.00
8.57
8.57
8.57
6.10
21.00
25.70
0.50
1.75
2.47
7
7
9
23
6.70
6.70
8.61
8.22
8.22
10.57
6.10
22.00
27.00
0.50
1.76
2.60
7
7
12
26
5.92
5.92
10.15
7.27
7.27
12.46
6.10
22.00
27.00
0.50
1.76
2.87
7
9
9
25
6.16
7.92
7.92
7.56
9.72
9.72
6.10
22.00
27.00
0.50
1.76
2.87
9
9
9
27
7.33
7.33
7.33
9.00
9.00
9.00
6.10
22.00
27.00
0.50
1.77
2.87
2) Ducted
Combination of indoor unit
Rated capacity for each indoor
unit (kBtu/h)
Maximum capacity for each in-
door unit (kBtu/h)
Total capacity
(kBtu/h)
Input power (kW)
Room 1
Room 2
Room 3
Total
Room 1
Room 2
Room 3
Room 1
Room 2
Room 3
Min.
Rated
Max.
Min.
Rated
Max.
7
9
-
16
7.09
9.11
-
8.66
11.14
-
6.10
16.20
19.80
0.50
1.44
1.83
7
12
-
19
7.07
12.13
-
8.33
14.27
-
6.10
19.20
22.60
0.50
1.79
2.23
7
18
-
25
6.16
15.84
-
7.20
18.50
-
6.10
22.00
25.70
0.50
2.09
2.87
9
9
-
18
9.00
9.00
-
10.75
10.75
-
6.10
18.00
21.50
0.50
1.70
2.12
9
12
-
21
9.00
12.00
-
10.11
13.49
-
6.10
21.00
23.60
0.50
1.88
2.55
9
18
-
27
7.33
14.67
-
8.67
17.33
-
6.10
22.00
26.00
0.50
2.09
2.87
12
12
-
24
11.00
11.00
-
12.50
12.50
-
6.10
22.00
25.00
0.50
2.08
2.84
7
7
9
23
6.70
6.70
8.61
8.22
8.22
10.57
6.10
22.00
27.00
0.50
1.81
2.65
7
7
12
26
5.92
5.92
10.15
7.27
7.27
12.46
6.10
22.00
27.00
0.50
2.11
2.87
7
9
9
25
6.16
7.92
7.92
7.56
9.72
9.72
6.10
22.00
27.00
0.50
2.11
2.87
9
9
9
27
7.33
7.33
7.33
9.00
9.00
9.00
6.10
22.00
27.00
0.50
2.12
2.87
NOTES:
Specifications are based on the following conditions.
• Power source of specifications: 230 V
• 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 15: 14,000 Btu/h, 18: 18,000 Btu/h
• 2 or more indoor units should be connected.
• Cooling: Indoor temperature of 80 °FDB (26.7 °CDB)/ 67 °FWB (19.4 °CWB), and outdoor tem-
perature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
• Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit—Indoor unit]
• The total ability of connected indoor units is from 14,000 Btu up to 27,000 Btu.
• Non-Ducted system combinations input are based on wall mount models. The input of combina-
tions including cassette models may be a little higher.
• Ducted system combinations capacities are based on slim duct units excepting 7,000-Btu mod-
els. 7,000 Btu models are based on wall mount models.
¢
Model: AOU24RLXFZ
- 213 -
6-1. Combinations
6. Capacity table
OUTDOOR UNIT
AOU24RLXFZ
OUTDOOR UNIT
AOU24RLXFZ
Содержание AGU12RLF
Страница 8: ......
Страница 183: ...Part 2 OUTDOOR UNIT 2 ROOMS TYPE MULTI TYPE AOU18RLXFZ ...
Страница 213: ...Part 3 OUTDOOR UNIT 3 ROOMS TYPE MULTI TYPE AOU24RLXFZ ...
Страница 255: ...Part 4 OUTDOOR UNIT 4 ROOMS TYPE MULTI TYPE AOU36RLXFZ1 ...