41
□
9. Check Alarm/Control Panel and Air blower.
•
Check to be sure that Alarm/Control Panel is located in a secure, accessible location.
•
Check fittings and wire connections; they should be tight and secure. This includes connection
between air hose and pressure switch.
•
Important: Check to be sure that all panel penetrations are air and watertight. Be sure no gas
from treatment system can leak into Alarm/Controller.
•
Be sure electrical cord between blower and outlet is free and clear and no object is on cord.
•
Check to be sure that panel is closed, secure and toggle switch is set to “Normal” setting.
•
If alarm exists by Diaphragm is damaged or auto-stop function is activated, replace the
Diaphragm kid or re-insert the auto-stop piece.
•
If alarm exists, check if blower is electrified and replace the power cable, the auto-stop piece
or the electric magnet.
□
10. Final Site Preparation.
•
Close and secure all access covers.
•
Close and secure blower cover.
□
11. Owner Communication
•
Be sure that business owner has a copy of the Fuji Clean USA Warranty information.
•
Be sure that service provider contact information is affixed to Alarm/Control Panel.
Warranty Activation. To activate system warranty, Fuji Clean USA must receive Warranty Activation Card!