FS
‐
Curtis
Page
30
Parameter Set
Value
Function
Password
To View
Password
To Edit
Device
Address No.
1 if the compressor set is a standalone
unit or the master unit in an
interconnected group.
2, 3 or 4 if the compressor set is a slave
unit in an interconnected group. Each
unit must have a unique address
number.
1 is the standard setting.
Connected device
identification.
Service Service
Parity
Checking
None
Transmission error
checking.
Service Service
Baud Rate
38400 bps
Data transmission
rate.
Service Service
Data Bits
8
Data bits per byte
in a Modbus
message.
Service Service
Stop Bits
1 bit
Stop bits per byte in
a Modbus
message.
Service Service
Note:
After making any changes to the set values, press on the back (
) button to exit from this menu. The
compressor set must then be powered off and back on again for the changes to take effect.
Note:
All devices on the interconnected network must have the same RS-485 communication settings
except for the device addresses that must be assigned uniquely.
Note:
For ease of setup, operation and maintenance, it is recommended that each compressor set in an
interconnected group be physically labelled with its address number, e.g. “Compressor #1”.
2.14 Language Menu
The language menu is accessed via the system menu. Log-in with the user password to view the parameter
choices or change the set value. The language menu screen is shown in Figure 2.15.