22
PB
OPERATION
Air flow direction (Louvers) control
The louver is operated by a stepper motor and operates the horizontal swing of the louver automatically. Press the SWING
button to start or stop the louver swing.
During the louver swing in normal operation, the current position will be stored. When the appliance turns off and the louvers
swing automatically to the default position, it will position at the close position plus 5º.
4-way valve
State: It is disengaged in cooling.
Switchover: When initially powered on for cooling, the 4-way valve is disengaged immediately.
When the heating is changed to the cooling, it needs an interval of 50 seconds for the 4-way valve to change over from being
engaged to being disengaged.
Cooling = No power to valve
Heating = Power to valve
Heating-run mode
Temperature compensation
The temperature compensation is 5º in heating mode. For example, if the set temperature is 77ºF(25°C) by the remote
control, when the room temperature is detected with 88ºF(31°C), the compressor will turn off. The main reason is that the hot
air is condensed at the top of the house.
Note: The compensation is available only if the room temperature sensor of indoor unit is used and it is not available when it
is subject to the sensor on the remote control.
Indoor fan motor operation
Anti-cold air system:
When the appliance run in Heat mode condition, the indoor fan motor operation is shown in Figure 303 to prevent the cooling
air come out during the appliance operation.
95ºF
86°F
77°F
When the difference between the setting temperature and the room temperature equal to 2º or 4º, the indoor fan speed will
keep in current speed.
Air flow direction control
The horizontal louver is controlled by a step motor, press the SWING button to swing or stop the louver.
During the louver run in normal operation, the current position will be stored. When the appliance turn off and louver swing
automatically to the default position, it will position at the default position plus 5º.
Outdoor fan
The outdoor fan speeds except single speed motor can be changed according to outdoor ambient temperatures.
4‑way valve
State: It is electrified in heating.
Switchover: When initially powered on for heating, the 4-way valve is activated immediately.
In the change from cooling to heating, it needs an interval of 50 seconds for the 4‑way valve to change over from being interrupted
to being activated.
The super function (option)
In cooling mode, when you press the SUPER button by remote control, the unit will operate for 15 minutes with the following
setting:
a. The set temperature is 16º(61°F);
b. The fan speed with highest speed;
c. The compressor runs with high frequency.
Figure 303
Содержание Floating Air Pro-Premiere FPHFW18A3A
Страница 25: ...25 INSTALLATION Installation Dimension Diagram Figure 401 ...
Страница 26: ...26 INSTALLATION Main Tools For Installation and Maintenance Figure 402 ...
Страница 34: ...34 INSTALLATION Install Outdoor Unit Fig 431 ...
Страница 35: ...35 INSTALLATION Outdoor Units ...
Страница 40: ...40 MAINTENANCE Fig 501 ...
Страница 59: ...59 TROUBLESHOOTING Error Code 13 Fig 708 Error Code 8 ...
Страница 62: ...62 TROUBLESHOOTING Error Code 20 DC fan motor test point Fig 711 ...
Страница 68: ...68 Fig 716 TROUBLESHOOTING Error Code 36 ...
Страница 73: ...73 COMPONENTS TESTING Fan Motor ...
Страница 87: ...87 WIRING DIAGRAMS Outdoor Units Figure 805 9 36K Outdoor Units ...