POWER CONNECTION CHART

GE 230/208 Volt

Wall Plug

Heater Wattage

Power Supply Kit

Configuration

Circuit Protective Device

@ 230/208 Volts

RAK3153A

Tandem

15-Amp Time-Delay Fuse or Breaker

2.55/2.09 KW

RAK3203A

Perpendicular

20-Amp Time-Delay Fuse or Breaker

3.45/2.82 KW

RAK3303A

Large Tandem

30-Amp Time-Delay Fuse or Breaker

5.00/4.09 KW

230/208 VOLT ELECTRICAL SUPPLY

A power supply kit must be used to supply power to the
Zoneline unit. The appropriate kit is determined by the
voltage, the means of electrical connection, and the
amperage of the branch circuit. See the POWER
CONNECTION CHART to confirm the appropriate kit.

All wiring, including installation of the receptacle, 
must be in accordance with the NEC and local codes,
ordinances, and regulations.

Installation instructions

RAK3153A, RAK3203A,

for your new

RAK3303A

Power Supply Kit for Cord
Connection with Current
Interruption Device

Before you begin – Read these instructions completely and carefully.
IMPORTANT – OBSERVE ALL GOVERNING CODES AND ORDINANCES.
Note to Installer – Be sure to leave these instructions with the Consumer.
Note to Consumer – Keep these instructions with your Owner’s Manual for future reference.

TOOLS NEEDED

1/4

Nut driver

Phillips screwdriver

This kit is for use with 230/208 volt 2800, 2900,
3800, 3900, 4100, 5200, 5500, 5800 and 6100
Series GE Zoneline units only.

IMPORTANT NOTES

This unit must be properly grounded.

The electrical rating marked on the previously installed
Zoneline and power supply kit must be the same as
the supply branch circuit.

Aluminum building wiring may present special
problems—consult a qualified electrician.

All wiring, including installation of the receptacle, 
must be in accordance with the NEC and local codes,
ordinances, and regulations.

Use ONLY the wiring size recommended for single
outlet branch circuit.

Proper current protection is the responsibility of 
the owner.

Tandem

15 Amp

230/208 volt receptacle configuration

Perpendicular

20 Amp

Large Tandem

30 Amp

Power supply kit

Recommended branch circuit wire sizes*

Nameplate

maximum circuit 

AWG wire

breaker size

size**

15A

14

20A

12

30A

10

AWG –  American Wire Gauge

*

Single circuit breaker from main box

** Based on copper wire, single-insulated conductor at 60°C

NOTE:

Use copper conductors only.

WARNING:

Disconnect the electrical power

supply before wiring connections.

Pub No. 31-61544     08-09 JR

Printed in the United States

Appearance may vary.