INSTALLATION
Leak Check, Evacuation, and Charging (Triple Evacuation)
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
CHARGE SYSTEM
EVACUATE
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS A VACUUM)
BREAK VACUUM WITH DRY NITROGEN
Capacity
(Btu/h)
Pipe Size
Standard
Length (ft)
Max.
Elevation
B (ft)
Max. Length
A (ft)
Additional
Refrigerant
(oz/ft)
LIQUID
GAS
9k-12
1/4"(Ø6.35)
3/8"(Ø9.52)
25
33
50
.22
18k
1/4"(Ø6.35)
1/2"(Ø12.7)
25
33
66
.22
24k-36k
3/8"(Ø9.52)
5/8"(Ø15.88)
25
33
66
.32
Fig. 437
Fig. 436