QUANTUM
™
LX EVAPORATOR CONTROL PANEL
COMMUNICATIONS SETUP
090.610-CS (MAY 2016)
Page 24
* Fan Status
Character
Position
Description of returned data
10, 17,
24, 31,
38, 45,
52, 59,
66, 73,
80
0 = Off
1 = Single Speed Running
2 = Two Speed Low
3 = Two Speed High
4 = Variable Speed Running
** Evaporator Status
Character
Position
Description of returned data
11, 18,
25, 32,
39, 46,
53, 60,
67, 74,
81
0 = Off
1 = Cooling/Dehumidification
2 = Satisfied
3 = Defrost
4 = Heating
5 = Start Delay
8 = Off-Alarm
9 = Cooling-Alarm
A = Satisfied-Alarm
B = Defrost-Alarm
C = Heating-Alarm
D = Start Delay-Alarm
*** Evaporator Mode
Character
Position
Description of returned data
12, 19,
26, 33,
40, 47,
54, 61,
68, 75,
82
0 = Off
1 = Mode 1
2 = Mode 2
3 = Mode 3 or Mode 4
4 = Pump Out
5 = Soft Hot Gas
6 = Hot Gas
7 = Bleed
8 = Fan Delay
RETURN CURRENT STATUS: $01Z3
Command structure:
Command Description
$
Start of command sequence.
ID
Quantum ID code.
Z3
Current Status for Units 23 - 30.
CS
Checksum
CR
Carriage Return
RETURNED ANSWER,
Character
Position
Description of returned data
1
[A]
= Acknowledge
2-3
[xx]
= Quantum ID code
4-5
[Z1]
= Current Status for units 23-30.
6-9
[+000]
= Control or Return Air Temp.
Unit
23
10
[0]
= Fan Status *
11
[0]
= Evaporator Status **
12
[0]
= Evaporator Mode ***
13-16
[+000]
= Control or Return Air Temp.
Unit
24
17
[0]
= Fan Status *
18
[0] = Evaporator Status **
19
[0]
= Evaporator Mode ***
20-23
[+000]
= Control or Return Air Temp.
Unit
25
24
[0]
= Fan Status *
25
[0]
= Evaporator Status **
26
[0]
= Evaporator Mode ***
27-30
[+000]
= Control or Return Air Temp.
Unit
26
31
[0]
= Fan Status *
32
[0]
= Evaporator Status **
33
[0]
= Evaporator Mode ***
34-37
[+000]
= Control or Return Air Temp.
Unit
27
38
[0]
= Fan Status *
39
[0]
= Evaporator Status **
40
[0]
= Evaporator Mode ***
41-44
[+000]
= Control or Return Air Temp.
Unit
28
45
[0]
= Fan Status *
46
[0]
= Evaporator Status **
47
[0]
= Evaporator Mode ***
48-51
[+000]
= Control or Return Air Temp.
Unit
29
52
[0]
= Fan Status *
53
[0]
= Evaporator Status **
54
[0]
= Evaporator Mode ***
55-58
[+000]
= Control or Return Air Temp.
Unit
30
59
[0]
= Fan Status *
60
[0]
= Evaporator Status **
61
[0]
= Evaporator Mode ***
83-86
CS (Checksum followed by Carriage return,
Line feed.)
Содержание QUANTUM LX Control Panel
Страница 12: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 12...
Страница 34: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 34...
Страница 50: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 50...
Страница 102: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 102...
Страница 103: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 103 SECTION 8 Q5 CONTROLLER...
Страница 110: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 110...
Страница 111: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 111 SECTION 9 Q4 CONTROLLER...
Страница 123: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 123 SECTION 10 APPENDICES...