IO Slave
(9) Wire Replacement Tab
(Figure 20)
Digital Out 1
– Select the desired FGRIO Master Digital Input # (1-4) to control the
IO Slave Digital Output # 1.
Digital Out 2
– Select the desired FGRIO Master Digital Input # (1-4) to control the
IO Slave Digital Output # 2.
Digital Out 1 Default
– Select the desired IO Slave Output Default at power-on and link
failure.
Open Drain output ON (Conducting to GND, 2 Amps max)
Open Drain output OFF (Non-Conducting)
Make no change in state.
Digital Out 2 Default -
Select the desired IO Slave Output Default at power-on and link
failure.
Open Drain output ON (Conducting to GND, 2 Amps max)
Open Drain output OFF (Non-Conducting)
Make no change in state.
Note:
If programming a DO to turn on after loss of link, ensure that the energized device
can sustain the state undamaged in case the loss in lengthy.
Default Delay
- This value is set in .28 second units. This sets the time duration that will
pass, after a loss of communication, before the radio enters default condition. E.g. A value
of 36 = 36*0.28 seconds = 10.08 seconds.
DI1 Pull Up/Down
– These options control power-up states of the internal resistor
(10Kohms) connected to the DIs. They can pull up, such as when using a closed-contact-to-
GND switch input, pull down so that unused inputs read “0” as DIs or ~0 as auxiliary ana-
logs, or float to not load analog inputs.
Note:
Both of the IO Slave Digital Outputs may be driven by the same FGRIO
Master Input.