Set Up With HyperTerminal (cont.)
IO Slave-
In order for the FGRIO System to function properly, the following settings must be
programmed. For all other settings not listed below, please refer to the User Manual.
(0) Operation Mode
(E)
FGRIO Slave
(2) Call Book–
The FGRIO Master’s serial number must be programmed as entry #0 in the IO
Slave’s Call Book. Set “Entry to Call” to 0. In addition, the Network ID must be set to the
same ID as the rest of the network. Programming both the Call Book and Network ID set-
tings is unique only to the FGRIO System and must be done for both integrated and stand
alone applications.
(3) Radio Transmission Characteristics
(1) Max Packet Size and (2) Min Packet Size–
The FGRIO System requires a minimum
combined packet size of 48 Bytes. The following is a list of the available packet sizes
that can be used (Figure 11, next page).
Fig. 10
RSPSupply - 1-888-532-2706 - www.RSPSupply.com