3) Radio Transmission Characteristics Tab-
(Figure 14)
Max Packet Size and Min Packet Size–
The FGRIO System requires a minimum com-
bined packet size of 48 Bytes. See Figure 6 (pg. 10) for a list of available packet sizes.
RF Data Rate–
The RF Data Rate must be set to “Normal” (3) when using the FGRIO Sys-
tem. This is for applications that are stand alone or when integrated into an existing FGR
network.
Set Up with Tool Suite (cont.)
Figure 14
5) MultiPoint Parameters Tab–
(Figure 15)
Number Repeaters
– This setting must be set to 1 for all FGR and FGRIO radios in the
Network.
Network ID–
In addition to entering the serial numbers of the IO Slaves in the Call Book,
the Network ID being used for the Network must be set from 1-4095 (Do NOT use 255).
Programming both the Call Book and Network ID settings is unique to the FGRIO System
and must be done for both integrated and stand alone applications.
Note: The FGRIO Master does not function as a Slave/Repeater in the SCADA network.
Figure 14
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-20028-FreeWave-FGR2-IO-IOE-Radio-Enclosed-900-MHz-I/O-Slave-Radio.aspx