Er.19  

-  checksum error of the loaded parameter set 

           WARNING! New data from the selected parameter set were loaded into the 

working area, however they shouldn’t be used as they could contain 
incorrect data. 

            solution: Quit the signalization and repeat the READ operation. If the                 
                           failure occures again, read another parameter set. 

 

Er.20  

-  the drive was running when the command READ/PROG was entered 

           solution: Quit the signalization, stop the drive, and repeat the READ/PROG   
                          command. 

 

Er.21        

- the identificator of the selected parameter set must be displayed when the      

                   READ/PROG command is beeing entered. 

          solution: Quit the signalization, select the parameter SET from menu,   
                         display and set its value to the desired parameter set identificator,  
                         and repeat the READ/PROG command. 

 

Er.22

 

 -  It is impossible to overprogram a factory set. 

 

Notes

 :   1)  When the failure 

Er.00

 or 

Er.01

 occures, the immediate automatic shut-  

                     

down of the inverter is realised and the motor runs freely down. 

       Available ways of reseting the drive depend on the parameter CRTR  
       setting. 

 

2)  

During the signalization of  

Er.00

 or 

Er.01

, all the keys are locked (ignored), 

except the LOC/REM key. If CRTR=1 and local control is switch on, the key 
STOP is also unlocked to enable the local RESET operation (refer to 
description of the parameter CRTR). 

 

3)  

During all other failure signalizations, the only unlocked keys are UP, 
DOWN, PAR and STOP. Pressing any of them quits the failure 
signalization. During local control, the STOP key in addition stops the drive. 

 

14

Содержание MINITERMINAL FIA-L

Страница 1: ...pod FRECON MINITERMINAL FIA L INSTALLATION AND USER MANUAL FRECON spol s r o Hodkovick 115 142 00 Praha 4 CZECH REPUBLIC tel 420 241 71 32 44 5 fax 420 241 72 10 52 E mail info frecon cz http www fre...

Страница 2: ...ual output frequency monitoring LCD screen operational status LED indication run fwd rev local control fault codes signalization MOUNTING externally anywhere convenient at a distance permitted by maxi...

Страница 3: ...setting keys Parameters and their values are adjusted by the three keys UP DOWN The keys UP DOWN enable selection of parameter code from parameter menu parameter value changing speed control in local...

Страница 4: ...g parameters reading from the set into the orki w ng area Press the READ key to read the values of all parameters from selected user set memory EEPROM or factory set memory ROM into the working area T...

Страница 5: ...ng down time depends on the moment of inertia of connected motor and load In the remote mode the STOP key is ignored 6 Control modes 6 1 REMOTE CONTROL terminals In the remote control mode the drive i...

Страница 6: ...frequency V f characteristic FBAS 25 0 241 0 Hz base nominal frequency max voltage reached U0 0 0 22 0 VMAX output voltage for FOUT 0 Hz U1 1 0 30 0 VMAX output voltage for FOUT 1 8 FBAS U2 2 0 40 0 V...

Страница 7: ...of the inverter output with error code Er 01 signalization for CINP 3 running up the drive with the substitutional output frequency reference set by parameter FERR Flashing FOUT value indicates that t...

Страница 8: ...invalid input signal was recognised and the substitutional value FERR is used as a frequency reference the output frequency can be out of the interval limited by values F0 and F100 8 3 Substitutional...

Страница 9: ...3x230V Fn 50 Hz FBAS 50 230 230 50 Hz Setting FBAS above the nominal value using the same load involves decreasing of the magnetic flux and available motor torque the drive is softer and the slip ris...

Страница 10: ...VMAX VMAX 0 FBAS f 0 FBAS f Linear V f curve Fan V f curve 8 6 Configuration parameters CINP determination of input analogue control signal for remote control setting of CINP doesn t affect local con...

Страница 11: ...the LOC REM key reseting the inverter using the STOP key and switching back after the rdy code is signalized to remote control However it is always necessary to find out and remove the failure reason...

Страница 12: ...any user set which preserves stored data when the power supply is switched off EEPROM memory The basic user set identified as UI 0 is the most important set as it determines initial setting of active...

Страница 13: ...tly used setting of functional parameters for the most common fans Initial setting of the active parameters in the working area During the initialisation after the inverter is powered on the data from...

Страница 14: ...cable strong interference near the cable solution Quit the failure signalization by pressing any of the keys UP DOWN PAR If the communication failure repeats check the cable and its connection to the...

Страница 15: ...from menu display and set its value to the desired parameter set identificator and repeat the READ PROG command Er 22 It is impossible to overprogram a factory set Notes 1 When the failure Er 00 or E...

Отзывы: