11.  Failures signalization 

When an operational failure or a parameter set manipulation error occures, the 
corresponding error code is signalized on the display as a flashing message  „

Er.NN

“, 

where NN is the numeric error identifier. 

 

11.1. Operational 

failures

 

 

Er.00

 

 

-  internal protection inverter shut-down 

                  cause: short circuit, overcurrent, Ixt, overvoltage, undervoltage, damaged   
                              motor, motor or power supply connection failure, motor windings   
                              connection failure 

           solution:  Find out the cause, clear the fault,  restart the drive. 

             Note:    A  strong  interference  source  near  the  inverter  can  cause  an 

accidental shut-down of the inverter. In this case the interference 
source should be removed, eliminated or suppressed using 
electromagnetic screen, noise suppressor or any other suitable 
interference suppressor or combination of them. 

 

Er.01

 

 -  inverter shut-down caused by an invalid input analogue signal during      

                     

remote control 

                                       cause:  The invalid input signal or incorrect parameter CINP setting 

   solution: Find out the cause, clear the fault, restart the drive. 

 

Er.02

 

 -  communication error between inverter and control pod 

cause:   Connection failure, too long cable, strong interference near the  
              cable 
solution: Quit the failure signalization by pressing any of the keys UP, 

DOWN, PAR. If the communication failure repeats, check the 
cable and its connection to the drive. If the failure still repeats, try 
to find out and eliminate the interference source, or reduce the 
cable length. 

 

Er.03

 

 -  software incompatibility 

cause:   The software versions of the inverter and control pod are    
              incompatible 
solution: se the control pod with a compatible software version. 

 

11.2. 

Parameter sets manipulation errors

 

 

Er.10 - Er.17

 

  -  EEPROM read/write failure 

            cause:   Accidental or repeated hardware failure 
            solution: If the failure occures accidentaly, you can quit the  
                          signalization by pressing any of the keys PAR, UP, DOWN,   
                          STOP. If not accidental, the hardware failure requires the  
                          service reparation. 

    WARNING !  If this failure occures during READ operation (loading the 

working area), it is necessary to repeat the READ operation as 
the working area may contain incorrect data. The RUN 
command must not be executed before correct data has been 
loaded into the working area. 

 

Er.18  

-   unusable data in the selected parameter set 

 cause: The set is empty (not yet programmed) or incompatible data format     
               was recognized (such set can be also assumed as an empty set) 

             solution: Quit the signalization and load (READ) another parameter set. 

 

 
 
 

 

13

Содержание MINITERMINAL FIA-L

Страница 1: ...pod FRECON MINITERMINAL FIA L INSTALLATION AND USER MANUAL FRECON spol s r o Hodkovick 115 142 00 Praha 4 CZECH REPUBLIC tel 420 241 71 32 44 5 fax 420 241 72 10 52 E mail info frecon cz http www fre...

Страница 2: ...ual output frequency monitoring LCD screen operational status LED indication run fwd rev local control fault codes signalization MOUNTING externally anywhere convenient at a distance permitted by maxi...

Страница 3: ...setting keys Parameters and their values are adjusted by the three keys UP DOWN The keys UP DOWN enable selection of parameter code from parameter menu parameter value changing speed control in local...

Страница 4: ...g parameters reading from the set into the orki w ng area Press the READ key to read the values of all parameters from selected user set memory EEPROM or factory set memory ROM into the working area T...

Страница 5: ...ng down time depends on the moment of inertia of connected motor and load In the remote mode the STOP key is ignored 6 Control modes 6 1 REMOTE CONTROL terminals In the remote control mode the drive i...

Страница 6: ...frequency V f characteristic FBAS 25 0 241 0 Hz base nominal frequency max voltage reached U0 0 0 22 0 VMAX output voltage for FOUT 0 Hz U1 1 0 30 0 VMAX output voltage for FOUT 1 8 FBAS U2 2 0 40 0 V...

Страница 7: ...of the inverter output with error code Er 01 signalization for CINP 3 running up the drive with the substitutional output frequency reference set by parameter FERR Flashing FOUT value indicates that t...

Страница 8: ...invalid input signal was recognised and the substitutional value FERR is used as a frequency reference the output frequency can be out of the interval limited by values F0 and F100 8 3 Substitutional...

Страница 9: ...3x230V Fn 50 Hz FBAS 50 230 230 50 Hz Setting FBAS above the nominal value using the same load involves decreasing of the magnetic flux and available motor torque the drive is softer and the slip ris...

Страница 10: ...VMAX VMAX 0 FBAS f 0 FBAS f Linear V f curve Fan V f curve 8 6 Configuration parameters CINP determination of input analogue control signal for remote control setting of CINP doesn t affect local con...

Страница 11: ...the LOC REM key reseting the inverter using the STOP key and switching back after the rdy code is signalized to remote control However it is always necessary to find out and remove the failure reason...

Страница 12: ...any user set which preserves stored data when the power supply is switched off EEPROM memory The basic user set identified as UI 0 is the most important set as it determines initial setting of active...

Страница 13: ...tly used setting of functional parameters for the most common fans Initial setting of the active parameters in the working area During the initialisation after the inverter is powered on the data from...

Страница 14: ...cable strong interference near the cable solution Quit the failure signalization by pressing any of the keys UP DOWN PAR If the communication failure repeats check the cable and its connection to the...

Страница 15: ...from menu display and set its value to the desired parameter set identificator and repeat the READ PROG command Er 22 It is impossible to overprogram a factory set Notes 1 When the failure Er 00 or E...

Отзывы: