8. Detailed description of displayable values and adjustable drive 
    parameters

 

8.1. Actual and required output frequency 

 

FOUT 

-

 

actual output frequency value 

 

 

 

- display / setting range : 

 

0.00 - 125.0   Hz 

 
When the drive runs the actual output frequency FOUT follows the value of frequency 
reference FSET considerating acceleration/deceleration limits ACC/DEC. 

 

In the remote control mode the frequency reference FSET, and consequently the 
output frequency, are limited by values F0 and F100. The only exception is possible 
when the substitutional output frequency reference FERR outside the limits F0, F100 is 
used (refer to description of parameters F0, F100, FERR and CINP). 
In the local control mode the actual output frequency can be changed by UP/DOWN 
keys in the whole range 0.00-125.0 Hz. 

 

When the drive is stopped, the code „

rdy

“ is displayed, instead of zero value, indicating 

that the drive is stopped but ready to run.

 

 

Flashing code „

-rdy

“ indicates that in stop state, remote control selected and 

CINP=2(3), an invalid analogue control signal (decreased under 2.5mA or 1.3V) is 
beeing recognized. In this case the command „RUN“ will cause: 

 

• 

for CINP=2 - immediate shut-down of the inverter output with error code „Er.01“  

 

                              signalization

 

• 

for CINP=3 - running up the drive  with  the substitutional output frequency   

 

                          reference  set  by parameter FERR

 

 

Flashing FOUT value indicates that the drive is running using the substitutional 
frequency reference. Refer to description of parameters FERR and CINP.

 

 

FSET

 

 

- required output frequency (i.e. frequency reference) value 

 

 

 

            - display / setting range : 

 

0.00 - 125.0   Hz 

 

In the remote control mode the value of FSET is driven by input analogue contol signal 
according to setting of parameters F0, F100 and CINP. 
The FSET value can be monitored also during stop state, when the output frequency is 
zero and the output of inverter is not active. 
Flashing FSET value („0.00“ for CINP=2  or  „<FERR>“ for CINP=3) indicates an invalid 
input analogue control signal. 

 

In the local control mode the value of FSET can be changed (controlled) only by 
UP/DOWN keys, and in the whole range  0.00-125.0 Hz. 

 

8.2. Analogue signal - to - frequency reference   conversion parameters 
       (limit values of output frequency for remote control) 

 

F0

 

- required output frequency related to input analogue signal of 0% of the selected   

                 

range, i.e.    0V / 0mA  for CINP=1,2   or   2V / 4mA  for CINP=3,4

 

 

F100 

-

 

required output frequency related to input analogue signal of 100% of the selected 

                   range, i.e.    10V / 20mA    for all settings of parameter CINP

 

 

             

- setting range : 

 

0.00 - 125.0   Hz 

 

 

6

Содержание MINITERMINAL FIA-L

Страница 1: ...pod FRECON MINITERMINAL FIA L INSTALLATION AND USER MANUAL FRECON spol s r o Hodkovick 115 142 00 Praha 4 CZECH REPUBLIC tel 420 241 71 32 44 5 fax 420 241 72 10 52 E mail info frecon cz http www fre...

Страница 2: ...ual output frequency monitoring LCD screen operational status LED indication run fwd rev local control fault codes signalization MOUNTING externally anywhere convenient at a distance permitted by maxi...

Страница 3: ...setting keys Parameters and their values are adjusted by the three keys UP DOWN The keys UP DOWN enable selection of parameter code from parameter menu parameter value changing speed control in local...

Страница 4: ...g parameters reading from the set into the orki w ng area Press the READ key to read the values of all parameters from selected user set memory EEPROM or factory set memory ROM into the working area T...

Страница 5: ...ng down time depends on the moment of inertia of connected motor and load In the remote mode the STOP key is ignored 6 Control modes 6 1 REMOTE CONTROL terminals In the remote control mode the drive i...

Страница 6: ...frequency V f characteristic FBAS 25 0 241 0 Hz base nominal frequency max voltage reached U0 0 0 22 0 VMAX output voltage for FOUT 0 Hz U1 1 0 30 0 VMAX output voltage for FOUT 1 8 FBAS U2 2 0 40 0 V...

Страница 7: ...of the inverter output with error code Er 01 signalization for CINP 3 running up the drive with the substitutional output frequency reference set by parameter FERR Flashing FOUT value indicates that t...

Страница 8: ...invalid input signal was recognised and the substitutional value FERR is used as a frequency reference the output frequency can be out of the interval limited by values F0 and F100 8 3 Substitutional...

Страница 9: ...3x230V Fn 50 Hz FBAS 50 230 230 50 Hz Setting FBAS above the nominal value using the same load involves decreasing of the magnetic flux and available motor torque the drive is softer and the slip ris...

Страница 10: ...VMAX VMAX 0 FBAS f 0 FBAS f Linear V f curve Fan V f curve 8 6 Configuration parameters CINP determination of input analogue control signal for remote control setting of CINP doesn t affect local con...

Страница 11: ...the LOC REM key reseting the inverter using the STOP key and switching back after the rdy code is signalized to remote control However it is always necessary to find out and remove the failure reason...

Страница 12: ...any user set which preserves stored data when the power supply is switched off EEPROM memory The basic user set identified as UI 0 is the most important set as it determines initial setting of active...

Страница 13: ...tly used setting of functional parameters for the most common fans Initial setting of the active parameters in the working area During the initialisation after the inverter is powered on the data from...

Страница 14: ...cable strong interference near the cable solution Quit the failure signalization by pressing any of the keys UP DOWN PAR If the communication failure repeats check the cable and its connection to the...

Страница 15: ...from menu display and set its value to the desired parameter set identificator and repeat the READ PROG command Er 22 It is impossible to overprogram a factory set Notes 1 When the failure Er 00 or E...

Отзывы: