RUN

   

command RUN - start of the drive (local control) 

 

 

When the drive is stopped (indicator RUN is off) and local control is selected (indicator 
LOC lights), the keystroke on RUN causes the drive to start rotation in selected direction 
(indicators FWD/REV). The output frequency increases from zero up to required 
frequency, which is set by the value of frequency reference FSET. The acceleration is 
driven by parameter ACC. (Note: Pressing UP or DOWN key during acceleration causes 
immediate stopping of acceleration as the value of frequency reference FSET is 
overwriten by the value of current output frequency.) 
In the remote control mode the RUN key is ignored. 

 

STOP

 

command STOP - stop of the drive (local control) 

 

 

In the local mode the keystroke on STOP causes stopping of the drive and deactivation 
of the 3-phase output of the inverter. The way of running down is selected by parametr 
CSTP: 

• 

CSTP = 0 - ramp mode (controlled run down), i.e. after command STOP the output 
frequency decreases down to zero with deceleration driven by parameter DEC. After 
reaching zero frequency the drive is still braked for about 30 ms by DC voltage, value 
of which is set by parameter U0. Then the output of inverter is deactivated. 

• 

CSTP = 1 - coast to stop mode (free run down), i.e. immediately after command 
STOP the output of inverter is deactivated and the motor runs down freely. The 
running down time depends on the moment of inertia of connected motor and load. 

In the remote mode the STOP key is ignored. 

 

6.  Control modes 

6.1.  REMOTE CONTROL (terminals)

 

In the remote control mode the drive is operated by control signals connected to terminals. 
One analogue control signal (voltage 0-10V / 2-10V, current 0-20mA / 4-20mA, or 
potentiometer) and two digital control signals RUN/STOP and FWD/REV are used. The 
analogue signal controls the output frequency, i.e. the speed of the drive. The digital signals 
control start, stop and direction of rotation of the drive. The analogue signal - to - output 
frequency reference conversion is determined by parameters F0, F100 and CINP. 
These signals can be controlled by a control system, PLC, FRECON TELECONTROL, or any 
other way. If a miniterminal is connected to a drive, the local control keys are ignored, when 
the remote control mode is selected. 

 

6.2.  LOCAL CONTROL (keypad)

 

In the local control mode the drive is fully operated by the control pod FRECON 
MINITERMINAL. The local control keys enable to start and to stop the drive, to change the 
direction of rotation, to set the output frequency reference FSET, or to control directly the 
actual output frequency FOUT in the full range 0-125 Hz with 0.01 Hz resolution, 
independently on the setting of parameters F0, F100 and CINP. 
One single keystroke on UP/DOWN keys changes the value of FSET or FOUT by one step, 
i.e. 0.01 Hz, longer pressing causes faster continuous changing of the value.  
In the local control mode the remote control signals from terminals are ignored. 

 

 
 
 
 
 

 

4

Содержание MINITERMINAL FIA-L

Страница 1: ...pod FRECON MINITERMINAL FIA L INSTALLATION AND USER MANUAL FRECON spol s r o Hodkovick 115 142 00 Praha 4 CZECH REPUBLIC tel 420 241 71 32 44 5 fax 420 241 72 10 52 E mail info frecon cz http www fre...

Страница 2: ...ual output frequency monitoring LCD screen operational status LED indication run fwd rev local control fault codes signalization MOUNTING externally anywhere convenient at a distance permitted by maxi...

Страница 3: ...setting keys Parameters and their values are adjusted by the three keys UP DOWN The keys UP DOWN enable selection of parameter code from parameter menu parameter value changing speed control in local...

Страница 4: ...g parameters reading from the set into the orki w ng area Press the READ key to read the values of all parameters from selected user set memory EEPROM or factory set memory ROM into the working area T...

Страница 5: ...ng down time depends on the moment of inertia of connected motor and load In the remote mode the STOP key is ignored 6 Control modes 6 1 REMOTE CONTROL terminals In the remote control mode the drive i...

Страница 6: ...frequency V f characteristic FBAS 25 0 241 0 Hz base nominal frequency max voltage reached U0 0 0 22 0 VMAX output voltage for FOUT 0 Hz U1 1 0 30 0 VMAX output voltage for FOUT 1 8 FBAS U2 2 0 40 0 V...

Страница 7: ...of the inverter output with error code Er 01 signalization for CINP 3 running up the drive with the substitutional output frequency reference set by parameter FERR Flashing FOUT value indicates that t...

Страница 8: ...invalid input signal was recognised and the substitutional value FERR is used as a frequency reference the output frequency can be out of the interval limited by values F0 and F100 8 3 Substitutional...

Страница 9: ...3x230V Fn 50 Hz FBAS 50 230 230 50 Hz Setting FBAS above the nominal value using the same load involves decreasing of the magnetic flux and available motor torque the drive is softer and the slip ris...

Страница 10: ...VMAX VMAX 0 FBAS f 0 FBAS f Linear V f curve Fan V f curve 8 6 Configuration parameters CINP determination of input analogue control signal for remote control setting of CINP doesn t affect local con...

Страница 11: ...the LOC REM key reseting the inverter using the STOP key and switching back after the rdy code is signalized to remote control However it is always necessary to find out and remove the failure reason...

Страница 12: ...any user set which preserves stored data when the power supply is switched off EEPROM memory The basic user set identified as UI 0 is the most important set as it determines initial setting of active...

Страница 13: ...tly used setting of functional parameters for the most common fans Initial setting of the active parameters in the working area During the initialisation after the inverter is powered on the data from...

Страница 14: ...cable strong interference near the cable solution Quit the failure signalization by pressing any of the keys UP DOWN PAR If the communication failure repeats check the cable and its connection to the...

Страница 15: ...from menu display and set its value to the desired parameter set identificator and repeat the READ PROG command Er 22 It is impossible to overprogram a factory set Notes 1 When the failure Er 00 or E...

Отзывы: