72
PRIMARY-22: HOA Type
HOA Type
22) Keyboard HOA
0 - Keypad HOA
1 - Auto Only
2 - Keypad Off/Auto
3 - External HOA
Default: (0) Keypad HOA
0
‐
VFD
HOA:
Fully
functional
HOA
keypad.
1
‐
Auto
Only
‐
HOA
is
Disabled
&
VFD
is
always
in
Auto
mode,
no
changes
by
HOA
keys.
2
‐
Hand
Disabled
‐
Fully
functional
Auto
Mode
and
VFD
can
be
stopped
by
HOA
in
OFF.
No
Hand
Mode.
3
‐
If
External
HOA
is
selected,
two
digital
inputs
should
be
set
to
Hand
and
Auto
and
HOA
switch
should
be
wire
to
those
inputs.
(If
both
DIs
are
activated=
Hand).
Refer
to
Fig.
04
and
Fig.
05
below.
PRIMARY-23: Run Command in Hand
Hand Run Cmd
23) Always Run
0 - HOA in Hand
1 - Terminal
2 - 3-Wire
3 - Comms
Default: (0) HOA in
Hand
Selections
for
Run
Command
in
HOA
Hand
position.
VFD
starts
when:
0
‐
HOA
is
in
Hand;
1
‐
HOA=
Hand
and
selected
terminal
is
activated;
2
‐
HOA=Hand
&
Start
Button
is
pressed,
6
‐
HOA=
Hand
&
start
command
is
given
via
comms.
PRIMARY-24: Speed Reference in Hand
Hand Speed Ref
24) Keypad
0 - Keypad
1 - 1A Analog Input
2 - 2A Analog Input
3 - Communications
4 - 3A Analog Input
Default: (0) Keypad
Selections
for
Speed
Reference
in
HOA
Hand
position.
When
HOA
is
in
Hand
position,
PID
mode
is
disabled.
2A
is
available
when
2A
DIP
Switch
is
set
to
Input.
PRIMARY-27: Keypad Frequency
Keypad Frequency
27) 15Hz
Min: PRIMARY-10 (Low
Frequency)
Max: PRIMARY-9 (High
Frequency)
Default: 15Hz
Freq
reference
via
keypad
in
Hand
or
Auto
Mode.
PRIMARY-30: Stop Mode
Stop Mode
30) Coast
Default: Decelerate
0 - Decel
1 - Coast
When
stop
command
is
received,
VFD
will
stop
based
on
selection:
DECEL
‐
Decrease
output
frequency
to
0Hz
per
Deceleration
Time
setting,
COAST
‐
immediately
stop
switch
and
motor
will
coast
to
a
stop
Содержание Q-link
Страница 12: ...12 2 1 2 UL Label...
Страница 15: ...15 CHAPTER 3 SPECIFICATIONS CHAPTER 3 SPECIFICATIONS 3 1 Standalone VFD Ratings 3 2 VFD Smart Bypass Ratings...
Страница 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Страница 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Страница 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Страница 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Страница 27: ...27 4 4 Wiring Schematic Smart Bypass...
Страница 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Страница 35: ...35 4 12 PID Control Diagram...
Страница 37: ...37 5 2 Control Interface...
Страница 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Страница 103: ...103 9 2 Fan Replacement...
Страница 104: ...104 9 3 Battery Replacement...
Страница 125: ...125 franklin controls com 1 800 962 3787 Thank you for choosing Franklin Control Systems formerly Cerus Industrial...