32
Description
Name
Type
Description
Details
Relay
Output
Terminal
O1
Terminal
Default
Selection:
Fault/N.O.
Fault,
Run
and
Proof
of
Run
relay
‐
SW
Configurable
(1.25A
@
125VAC,
Max
Switching
Voltage
250VAC)
O2
Terminal
Default
Selection:
Fault/N.O.
Wet
Input
Terminals
V1
Terminal
1
Default
Selection:
Speed
A/Active
High
(V)
Shutdown
/
Permissive
/
Fireman's
Override
/
Limit
Switch
/
Speed
A
/
Speed
B
/
None
‐
SW
configurable
(Default
N.O.)
12
‐
240VAC/VDC,
5mA
maximum
V2
Terminal
1
Common
1
V3
Terminal
2
Wet
Input
2
default:
External
Trip/Active
High
(V)
V4
Terminal
2
Common
2
Cooling
Fan
Fan
Connector
Fan
Power
Supply
Cooling
fan
for
VFD
(factory
wired)
Dry
Input
Terminals
D3
Terminal
Dry
Input
3
default:
None
Shutdown
/
Permissive
/
Fireman's
Override
/
Limit
Switch
/
Speed
A
/
Speed
B
/
None
‐
SW
configurable
(Default
N.O.)
24VDC
3mA
maximum
D4
Terminal
Dry
Input
4
default:
None
Analog
I/O
3A
Terminal
Input
(4–20mA)
Analog
PID
reference
or
speed
reference.
Max
Error
allowed
is
1%
of
Full
Scale
SG
Terminal
Signal
Ground/Shield
Signal
Ground
is
shared
between
terminals
D3/D4
and
3A
Relay
Output
2
03
Terminal
Default
Selection:
Fault/N.C.
Fault,
Run
and
Status
relay
‐
SW
Configurable
(1.25A
@
125VAC,
Max
Switching
Voltage
250VAC)
04
Terminal
Default
Selection:
Fault/COM
05
Terminal
Default
Selection:
Fault/N.O.
Analog Input (1A, SG) - The Analog Input mode is user selectable (0-10V, 0-24V or 4-
20mA) based on status of DIP switches.
Configurable Analog Input/Output (2A, SG) - The Analog Input/Output mode is user
selectable (0-10V input, or output 0-10V or 4-20mA) via DIP switches. When configured
as an input it only accepts an 0-10VDC input signal
.
As an output, it provides a
programmable/variable voltage or current.
Analog Input 3A is a dedicated 4-20mA input
Wet Inputs (V1-V2, V3-V4) - Voltage Input accepts AC/DC voltages 12-240V± 10%,
maximum current draw is 5mA. Inputs can be interchanged between N.O. and N.C.
Default state is Active High when voltage is present (N.O.).
Dry Inputs (D1, D2, D3, D4 SG) - Four Dry inputs with maximum current limit of 3mA are
available. Inputs can be interchanged between N.O. and N.C. Default contact state is
NO.
Power Outputs –
o
(A+, A-) The Damper Power output will be activated as soon as an active run
command from the VFD is initialized and provides 24V DC at 0.5A maximum. If
a limit switch or a timer is used, the VFD will not output until the switch closes or
timer expires.
(24, SG) The Control Power will output 24VDC at 50mA maximum. The Control Output will be
activated whenever the VFD is powered up to provide controls to sensors
Содержание Q-link
Страница 12: ...12 2 1 2 UL Label...
Страница 15: ...15 CHAPTER 3 SPECIFICATIONS CHAPTER 3 SPECIFICATIONS 3 1 Standalone VFD Ratings 3 2 VFD Smart Bypass Ratings...
Страница 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Страница 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Страница 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Страница 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Страница 27: ...27 4 4 Wiring Schematic Smart Bypass...
Страница 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Страница 35: ...35 4 12 PID Control Diagram...
Страница 37: ...37 5 2 Control Interface...
Страница 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Страница 103: ...103 9 2 Fan Replacement...
Страница 104: ...104 9 3 Battery Replacement...
Страница 125: ...125 franklin controls com 1 800 962 3787 Thank you for choosing Franklin Control Systems formerly Cerus Industrial...