88
8.7 View
Information
VIEW-1: VFD Output Frequency
Output Frequency
1)
Min: 0.0
Max: 240.00 [Hz]
Displays
the
VFD
output
frequency.
VIEW-2: Motor Speed
Motor Speed
2)
Min: 0.0
Max: 3600 [RPM]
Displays
the
current
RPM
of
the
motor.
VIEW-3: Wattmeter
Wattmeter
3)
Min: 0.0
Max: 4294967 [kWh]
Displays
the
current
Wattage
measurement.
VIEW-5: Average Output Current
Average Current
5)
Min: 0.0
Max: 6x VFD FLA [A]
Displays
the
Average
Output
Current.
VIEW-6: Line U Current
Line U Current
6)
Min: 0.0
Max: 6x VFD FLA [A]
Displays
the
Line
U
Current.
VIEW-7: Line V Current
Line V Current
7)
Min: 0.0
Max: 6x VFD FLA [A]
Displays
the
line
V
Current.
VIEW-8: Line W Current
Line W Current
8)
Min: 0.0
Max: 6x VFD FLA [A]
Displays
the
Line
W
Current.
VIEW-9: DC Bus Voltage
DC Bus Voltage
9)
Min: 0.0
Max: 1000.0
Displays
the
DC
bus
voltage.
VIEW-10: Output Voltage
Output Voltage
10)
Min: 0.0
Max: 600.0
Displays
the
VFD
calculated
output
voltage
(RMS).
VIEW-11: Output Status
Output Status
11)
0 - VFD Off
1 - Accelerate
2 - Decelerate
3 - Steady
4 - Speed search
5 - Flying start
6 - DC output
7 - Preheat
8 - DC trip prevention
9 - Stall prevention
10 - Bypass off
11 - Bypass run
Displays
the
output
status.
VIEW-12: System Status
System Status
11)
0 - VFD stop
1 - VFD run
2 - VFD disabled
3 - VFD fault
4 - VFD shutdown
5 - VFD fireman's
override
6 - VFD auto reset
8 - Power-on delay
12 - Signal loss
14 - PID run
15 - Open damper
18 - Bypass stop
19 - Bypass manual
20 - Bypass override
22 - Bypass auto on
fault
23 - Bypass disabled
24 - Bypass fault
25 - Bypass shutdown
27 - Bypass auto on
comms loss
Displays
the
current
system
operating
status.
Содержание Q-link
Страница 12: ...12 2 1 2 UL Label...
Страница 15: ...15 CHAPTER 3 SPECIFICATIONS CHAPTER 3 SPECIFICATIONS 3 1 Standalone VFD Ratings 3 2 VFD Smart Bypass Ratings...
Страница 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Страница 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Страница 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Страница 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Страница 27: ...27 4 4 Wiring Schematic Smart Bypass...
Страница 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Страница 35: ...35 4 12 PID Control Diagram...
Страница 37: ...37 5 2 Control Interface...
Страница 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Страница 103: ...103 9 2 Fan Replacement...
Страница 104: ...104 9 3 Battery Replacement...
Страница 125: ...125 franklin controls com 1 800 962 3787 Thank you for choosing Franklin Control Systems formerly Cerus Industrial...