77
8.3
VFD – Advanced Setup
Group
VFD-4: Auto Bypass
Auto Bypass
4) Disabled
0 - Disabled
1 - On VFD Fault
2 - Bypass Comm Loss
3 - VFD Fault & Bypass
Comm Loss
Default: Disabled
If
set
to
“On
VFD
Fault”
and
VFD
trips,
the
VFD
bypass
will
start
if
run
command
is
present.
If
set
to
“Bypass
Comm
Loss”
and
VFD
communication
is
not
present,
the
bypass
will
start.
If
set
to
both,
bypass
starts
when
either
VFD
‐
Bypass
comms
are
lost
or
VFD
is
in
Fault
mode.
VFD-6: Damper Control
Damper Control
6) Disabled
0 - Disabled
1 – Enabled
Default: (0) Disabled
Enables
Damper
or
Lubrication
Mode.
If
start
command
is
received,
VFD
will
provide
24VDC,
0.5A
to
a
damper
motor
and
after
Damper
delay
or
when
DSW
is
closed
VFD
will
start
motor.
VFD-7: Damper Delay
Damper Delay
7) 120s
Min: 0s
Max: 6000s
Default: 120s
1.
No
damper
limit
switch.
After
start
command
is
received,
VFD
will
provide
power
to
a
damper
motor
and
after
Damper
delay
it
will
start
the
motor.
There
is
no
damper
fault
by
limit
switch.
2.
If
a
digital
input
is
set
to
damper
SW
and
VFD
receives
run
command,
VFD
provides
power
to
damper
motor
and
after
limit
SW
is
closed,
it
will
start
a
motor.
If
SW
is
not
closed
within
time
delay,
VFD
will
trip
on
damper
fault.
Skip
Frequencies
There
are
three
sets
of
Skip
Frequency
pairs
of
parameters
that
let
you
Enable
or
Disable
or
set
Low
and
High
value
for
each
set.
The
description
below
applies
to
each
set
respectively:
Disabled:
Skip
frequency
is
disabled
Enabled:
Skip
frequency
allows
you
to
skip
from
the
VFD
reference
short
frequency
range
of
system
resonant
frequencies.
If
the
speed
reference
given
digitally
from
a
keypad
or
communication
is
set
to
a
value
in
the
skip
zone,
the
VFD
will
run
at
Low
Skip
Hz
until
the
speed
command
is
at
or
above
High
Skip
Hz.
Then
the
VFD
speed
reference
will
jump
from
Low
to
High
Skip
Hz
and
the
VFD
output
frequency
will
ramped
up
based
on
the
acceleration
time.
On
each
skip
zone,
the
only
condition
we
need
to
maintain
is
that
the
Skip
High
should
be
at
least
1Hz
greater
than
Skip
Low.
Between
zones
it
is
not
a
problem
if
the
2
nd
Skip
Zone
is
set
below
or
overlapping
the
1
st
one.
Low
Frequency
(Low
frequency
of
the
resonance
skip
zone)
:
If
analog
signal
or
communication
is
used
for
speed
reference,
the
VFD
will
continue
to
run
at
the
Low
Skip
Frequency
until
the
signal
value
is
at
or
greater
than
the
High
Skip
Frequency.
Then
the
VFD
will
ramp
‐
up
from
Low
to
High
skip
Hz
based
on
the
acceleration
time.
Range
0Hz
to
PRIMARY
‐
7
(Max
Frequency).
High
Frequency
(High
frequency
of
the
resonance
skip
zone
):
Range
‐
Low
Frequency
for
this
Skip
Frequency
to
PRIMARY
‐
7
(Max
Frequency).
Содержание Q-link
Страница 12: ...12 2 1 2 UL Label...
Страница 15: ...15 CHAPTER 3 SPECIFICATIONS CHAPTER 3 SPECIFICATIONS 3 1 Standalone VFD Ratings 3 2 VFD Smart Bypass Ratings...
Страница 16: ...16 3 3 VFD with Disconnect Ratings 3 4 VFD HP Rated Ratings...
Страница 18: ...18 3 8 Standalone and HP Rated VFD Dimensions...
Страница 19: ...19 3 9 Smart Bypass and VFD with Disconnect Dimensions...
Страница 26: ...26 4 3 Wiring Schematic Standalone HP Rated VFD s...
Страница 27: ...27 4 4 Wiring Schematic Smart Bypass...
Страница 28: ...28 4 5 Wiring Schematic VFD with Disconnect...
Страница 35: ...35 4 12 PID Control Diagram...
Страница 37: ...37 5 2 Control Interface...
Страница 95: ...95 ADMIN 35 Serial Number Serial Number 30 XXXXXXXX 0 99 999 999...
Страница 103: ...103 9 2 Fan Replacement...
Страница 104: ...104 9 3 Battery Replacement...
Страница 125: ...125 franklin controls com 1 800 962 3787 Thank you for choosing Franklin Control Systems formerly Cerus Industrial...