19
2-wire sensor module (2WSNS)
The 2-Wire Sensor Module (2WSNS) is designed to accept 12 sensor inputs per module, and the
system as a whole can accept a total of 36 sensors (3 modules with 12 inputs each). The 2WSNS
only supports standard sensors, and does not accept inputs from BRITESENSORs
®
. Refer to the
diagram below to identify some of the standard sensors that can be used with this module.
NOTE:
Standard sensors do not use digital data. They operate like ON/OFF switches, which are
closed when no liquid is present and open when a liquid is detected.
NOTE:
All components located in the hazardous area must be third-party certified and have
appropriate entity parameters.
NOTE:
More than one module is used to continue connections. See "Module configuration chart"
later in this chapter.
2-Wire Sensor Module
Number of Channels:
12
Safety Rating:
Class I, Division 1, Group D, [EEx ia] IIA
Entity Parameters
Uo = 6.51 V
Io = 2.04 mA
Co = 500 uF
Lo = 100 mH
Po = 3.3 mW
2-Wire Sensor
Module
RUN
ERR
9
8
7
–Blk
+Wht
–Blk
+Wht
–Blk
+Wht
12
11
10
–Blk
+Wht
–Blk
+Wht
–Blk
+Wht
3
2
1
–Blk
+Wht
–Blk
+Wht
–Blk
+Wht
6
5
4
–Blk
+Wht
–Blk
+Wht
–Blk
+Wht
- (BLK)
TSP-ULS
(universal liquid sensor)
Hazardous Location
Class I, Division 1, Group
D, Group IIA, Zone 0
Non-Hazardous
Location
Reed float switch opens when float
moves up approiximately 1/2" (13 mm)
(Red)
(Blk)
Magnetic
(Red)
(Blk)
C
NC
Gnd
In
3"
(76mm)
1.5"
(38 mm)
0.375"
(9.5 mm)
Содержание KWIK TRIP EVO 5000
Страница 6: ...Intentionally Blank ...
Страница 10: ...4 Intentionally Blank ...
Страница 65: ...59 Typical wiring cabinet layout ...
Страница 66: ...60 Intentionally Blank ...
Страница 83: ...Intentionally Blank ...
Страница 84: ...AG 013 r3 ...