64
Learn messages
Learn Message
Description
Learning 0 offset
Displayed when the ATG is calibrating 0
Excessive offset/unstable
Pressure is unstable
Learning pump operating pressure
Displayed when the ATG is learning the operating
pressure
Insufficient pressure
STP is not operating at a high enough pressure
No pressure loss
ATG does not detect a leak
Insufficient volume (line too small)
ATG detects a pressure drop that is too great
Learning pressure decay curve
Displayed during the learn process to indicate that the
calibrated leak decay curve is being recorded
Mod. Range error (line too big)
ATG detects a pressure drop that is too small
Learned
The line has been learned
Line status and control screens
The status of each line channel can be viewed at any time by navigating to the Line Status or
Control screens. To get to the Line Status or Control screens, go to
FMS > Status > Lines
or
FMS >
Control > Lines
.
LS500 status screen
The status of each line can be viewed at any time by navigating to the line status or control
screens.
Status and alarm Indicators
Description
Status
Indicates the condition of the line
Line Pressure
Indicates the current line pressure
Enabled
Green, enabled. Red, disabled
Not Learned
Red, if not learned. Gray, if learned