13
Standard installation materials
Recommended standard materials should be selected and installed per all applicable local, state
and federal codes governing the installation of this product and its associated systems. Please see
the corresponding ATG/module wiring section or the associated devices section of this manual
for complete installation details.
Cables required for liquid level probes, VFMs & 4-20 mA sensors
Use cables and wires compliant with national and local codes. FFS recommends using the types
of cable shown below up to a recommended length of:
•
Belden No. 87760 87760 (0.15” or 3.048 mm OD) to 260 feet (80 m)
•
Belden No. 87761* (0.12” or 3.048 mm OD) to 400 feet (120 m)
•
Belden No. 88761 88761 (0.12” or 3.048 mm OD) to 400 feet (120 m)
•
Belden No. 89182* (0.31” or 7.874 mm OD) to 1500 feet (450 m)
NOTE:
An asterisk (*) denotes a cable that may be ordered from FFS.
NOTE:
Conductors of different intrinsically safe (IS) circuits may be run together within the same
conduit, and, when they do, they should have at least .01 inches (.25 mm) of insulation and a
dedicated ground.
Cable or wire for 2-wire or 3-wire sensors
2-wire or 3-wire sensor wire (type THHN, TFFN, or THWN, gas and oil resistant, 18 AWG
minimum, 1500 feet max. wire run length) can be used when enclosed within rigid metal conduit-
from the sensor to the ATG. Leak detection sensor cable is required when not run through rigid
metal conduit. Refer to the Direct Burial Cable Installation Manual (P/N 000-1041) for further
information. See below for cable types and descriptions:
Alpha 58411 (FFS part number 600-0062)
Two conductor cable for standard,
2 conductor leak detection sensors
(0.114 inch (2.9 mm) O.D.)
Wires required for the ATGs
The following wires are required for EVO
TM
550 and EVO
TM
5000 ATGs.
•
3 conductors: Power, 14 GA to 12 GA maximum, black, white, and green.
•
1 conductor: Safety ground, 12 AWG, green. (Two may be required in some locations.)
•
As required conductors: Accessories, type THHN, TFFN, or THWN, 18 AWG minimum.
Circuit breaker
20 Amp
:
This provides power only for the T5 Series system. One is required per ATG.