LS-500 functional testing
Perform a Functional Test annually. This test verifies that the LS-500 application will detect and
alarm or a leak condition. Perform this test when there is no dispensing.
1.
If the channel is enabled, disable it. At the T5 ATG (via LCD or TSA), navigate to the FMS >
Lines Control screen. Click Enable/Disable to disable the line.
2.
Remove the plug in the needle valve kit on the manifold. Connect the TS-ALCAL (Leak
Generator Kit) to this port.
3.
Open the needle valve.
4. Enable the line. This will initiate a gross line test.
5.
Verify that the ATG displays a gross line test fail. This can take up to 10 minutes.
6.
The channel will be disabled by the FMS application. Remove the TS-ALCAL. Replace and
tighten the plug.
7.
At the T5 ATG (via LCD or TSA), navigate to the FMS Lines Control screen. Press Reset Alarm
to clear the alarm and enable the channel.
8.
Click OK when prompted.
9.
If the Annual Functional Test passed by properly detecting the leak, please skip this step. If
the system did not catch the leak and the test failed, disable the channel and run the
pre-operational tests. Perform the functional test again. If the system still fails to detect the
leak, please contact FFS Technical Support (1-800-984-6266).
Enabling or disabling lines
After learning the line(s), each line will need to be enabled to allow monitoring. The Line Status
reflects the current status.
Enabling lines
At the T5 ATG (LCD or TSA), navigate to the FMS Control screen. Click Enable/Disable to enable
the line. Only while the line is enabled will it continuously monitor and test pressure levels by
activating the STP as necessary.
Disabling line channels
At the T5 ATG (LCD or TSA), go to the FMS>Lines Control screen. Click Enable/Disable to disable
the line.
IMPORTANT
: While the line is Disabled, FMS will neither maintain nor test line pressure levels.
NOTE
: If alarms or errors occur, please refer to the "Alarms" section earlier in this chapter.