5
Splice Connector Kits
Use FFS-approved, moisture-resistant, no-strip splice connectors for liquid level probe and leak
detection sensor wires. (Order either TSP-KW30INSERT or FMP-CON30. Both kits contain 30 of
these connectors.) Using moisture-resistant splice connectors:
• Reduces or eliminates corrosion of the wire connections from repeated exposure to water
condensation, which causes eventual signal loss and system failure.
• Reduces or eliminates equipment damage from water flooding around the connectors,
which causes short-circuit damage.
Installing the console
Location
The place you select to install the console must be indoors in an area classified as non-hazardous.
(See the console specifications table in the "Wiring the console and modules" section.) To get the
maximum benefit from this system, install the console where personnel can easily make use of
it; mount it at eye level for operator convenience. Mount the console level on a vertical surface
between 2 feet (0.6 m) and 6 feet (1.9 m) high using the appropriate fasteners. For European
applications, the console must be located in a pollution degree 2 environment per IEC60664.
Mounting the console
The EVO
TM
600 and EVO
TM
6000 consoles must be mounted in a location where explosive or
flammable vapors are not present, otherwise an explosion hazard will be created which can result
in severe injury, death, serious property damage and/or environmental contamination.
Leave a minimum of two inches (5.1 cm) of space around the console open to allow for
ventilation, communication port connections, conduit and wiring. If the ventilation slots located
on the sides are obstructed, the unit may overheat and stop functioning as intended.
Four mounting tabs are available on the outside corners of the console. Select fasteners that have
sufficient load carrying capacity and which are appropriate for wall construction. A fully equipped
EVO
TM
600 can weigh up to 27 lbs (12 kg) and an EVO
TM
6000 console can weigh as much as 40 lbs
(18 kg), so make sure that your fasteners (and mounting surface) can adequately support that
much weight. In addition, plan ahead to make sure that there is enough room around the console
for conduit coming into the unit, communication port connections, possible incoming probe or
sensor wiring, and for the console door to fully open for easy access. For questions concerning
standard installation materials, please refer to the Standard Installation Materials section of this
manual.
Dimensions
Use the dimensions shown in the following drawings to aid you in mounting the console. Please
be aware that the conduit knockouts are located at the bottom of the unit and ventilation slats on
the sides of the unit, so remember to allow for sufficient space on the bottom and both sides of
the console during installation.