29
4-20mA Analog Input Module (420IB)
The 4-20mA Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA
interface. EVO
TM
600 and EVO
TM
6000 consoles can support up to 24 inputs (3 modules with 8
inputs each) and up to 48 inputs with an expansion console, depending on available space in your
console. The Analog Input Module will most likely be used with: line leak pressure transducers,
tank pressure sensors, and vacuum sensors.
Analog Input Module Specifications
Number of Channels:
8
Entity Parameters:
Uo = 26.25 V
Io = 98.2 mA
Co = 1.25
μ
F
Lo = 14.7 mH
Po = 0.64 W
4-20mA Input
Module
RUN
ERR
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
Vacuum
Sensor
+ (BLK)
- (White)
Tank Pressure Sensor
- (BLK)
+ (RED)
- (BLK)
+ (RED)
LSU500
Hazardous Location
Class I, Division 1, Group D,
Group IIA, Zone 0
Non-Hazardous
Location
FMP-TEM
- (BLK)
- (BLK)
+ (RED)
+ (BROWN)
- (BLK)
+ (RED)
+ (RED)
+ (WHT)
- (BLK)
NOTE:
All components located in the hazardous area must be Third Party Certified and have
appropriate Entity Parameters.