24
Probe Module (PRB)
The Probe Module (PRB) gathers data from LL2 and LL3 probes, UDP sensors (FMP-XXX-U), DMS
sensors, and Vapor Flow Meters. Each PRB can accommodate 12 devices and the EVO
TM
600 and
EVO
TM
6000 supports a total of 36 inputs (3 modules with 12 inputs each) or 72 inputs with an
expansion console.
Probe Module Specifications
Number of Channels:
12
Entity Parameters:
Uo = 28.35 V
Io = 157.5 mA
Co = 1.04 μF
Lo = 1.4 mH
Po = 1.1 W
Probe
Module
RUN
ERR
9
8
7
–Blk
+Red
–Blk
+Red
–Blk
+Red
12
11
10
–Blk
+Red
–Blk
+Red
–Blk
+Red
3
2
1
–Blk
+Red
–Blk
+Red
–Blk
+Red
6
5
4
–Blk
+Red
–Blk
+Red
–Blk
+Red
SHLD
- (BLK)
+ (RED)
SHLD
- (BLK)
+ (RED)
Non-Hazardous
Location
Hazardous Location
Class I, Division 1, Group D,
Group IIA, Zone 0
Probe
SHLD
Probe
Vapor Flow
Meter
NOTE:
All components located in the hazardous area must be Third Party Certified and have
appropriate Entity Parameters.
Содержание EVO 600