27
3-Wire Sensor Module (3WSNS)
This sensor module is designed to accept up to 8 sensor inputs per module, and the system as a
whole can accept up to a total of 24 sensors (3 modules with 8 inputs each) and up to 48 sensors
with an expansion console. The 3WSNS can support standard sensors and BRITESENSORs®.
BRITESENSORs® are powered sensors that digitally communicate the sensor–type and alarm
status of the sensor to the console. Most BRITESENSORs® can discriminate between water and
hydrocarbon products and produce different alarm codes for each. See the diagram below to
identify the types of sensors you should use with this module.
3-Wire Sensor Module
Number of Channels:
8
Entity Parameters:
Uo = 7.71 V
Io = 573 mA
Co = 500 μF
Lo = 433 μH
Po = 932 mW
3-Wire Sensor
Module
RUN
ERR
4
–Blk
Wht
+Red
3
–Blk
Wht
+Red
2
–Blk
Wht
+Red
1
–Blk
Wht
+Red
8
–Blk
Wht
+Red
7
–Blk
Wht
+Red
6
–Blk
Wht
+Red
5
–Blk
Wht
+Red
- (BLK)
+ (RED)
(WHT)
- (BLK)
FMP-ULS
or
TSP-ULS
(Universal Liquid Sensor)
(WHT)
FMP-EIS
or
TSP-EIS
(Electro-optical Interstitial sensor)
- (BLK)
+ (RED)
(WHT)
Non-Hazardous
Location
Hazardous Location
Class I, Division 1, Group D,
Group IIA, Zone 0
FMP-DTS
or
TSP-DTS
(Discriminating Turbine Sump Sensor)
NOTE
: UDP sensors (FMP-XXX-U) are supported on the Probe Module and are not supported on
the 3-Wire Sensor module.
Содержание EVO 600
Страница 1: ...EVOTM 600AND EVOTM 6000 AUTOMATICTANK GAUGES INSTALLATION GUIDE ...
Страница 37: ...33 Intentionally Blank ...
Страница 38: ...Intentionally Blank ...
Страница 39: ...Intentionally Blank ...
Страница 40: ...s228180033 r1 ...