30
RS-485 Module (FMP-485IS Module)
The RS-485 Module is an intrinsically safe module that can connect up to four independent
Mulitplexing Sensor Hubs (MSH). The communication to the MSHs is via RS-485 protocol. All
connections to this module must maintain intrinsically safe protocols.
Entity Parameters
Uo, V
10.71
lo, mA
563
Lo, mH
0.5
Co, μF
6.3
Po, W
1.22
RS-485
Module
RUN
ERR
Hazardous Location
Class I, Division 1, Group D,
Group IIA, Zone 0
Non-Hazardous
Location
Uo=10.71 V
lo=0.563 mA
Lo=0.5 mH
Co=6.3 μF
Po=1.22 W
PWR
A
B
GND
PWR
A
B
GND
PWR
A
B
GND
PWR
A
B
GND
563 mA
NOTE:
All components located in the hazardous area must be Third Party Certified and have
appropriate Entity Parameters.