17
NOTE:
If a dispenser’s current rating is between 2 and 10 amps, use a 10 Amp Relay Module.
Refer to the 10 Amp Relay Module section for details. The EVO
TM
600 and EVO
TM
6000 consoles
are limited to a total of three relay modules, regardless of the amperage rating and a total of
six modules with an expansion console. If the current rating is higher than 10 Amps, use an
appropriate extension relay.
Relay Module
RUN
ERR
NO8
C8
NC8
NO7
C7
NC7
NO6
C6
NC6
NO5
C5
NC5
NO4
C4
NC4
NO3
C3
NC3
NO2
C2
NC2
NO1
C1
NC1
DISPENSER 1
Relay Module disables
power to the dispenser
upon alarm conditions.
110/240 VAC
Electrical Panel
Line
Neutral
Line
Neutral
GND
Switching Current 2A Max.
Switching Power 1500 VA Max.
NOTE: This relay must be inverted in programming to operate properly.