Key to press
Description
Display
D
C
to select the heat output corresponding to the device
model
to confirm your selection and go back to the START
screen
G31
1. 115kW
2. 150kW
3. 200kW
4. 240kW
5. 280kW
to confirm
oK
Restores factory data
Please wait
to confirm
oK
- 47
-
INST
ALLA
TION
setting the "gas change" parameter determines AUTOMATiCALLY the number of fan revolutions indicated in the table.
descRiPtion
maui KR 115-280
115
150
200
240
280
Nominal heat output Min. ÷ Max.
21,0 ÷ 113,0 30,0 ÷ 150,0 35,5 ÷ 200,0 42,5 ÷ 235,0 49,5 ÷ 275,0
kW
Operating rpm
with
G20
1665 ÷ 7400 1650 ÷ 6250 1230 ÷ 5600 1320 ÷ 5800 1300 ÷ 5800
rpm
Frequency
55.5 ÷ 246.7
55 ÷ 208.3
61.5 ÷ 280
66 ÷ 290
65 ÷ 290
hz
Operating rpm
with
G31
1665 ÷ 7400 1650 ÷ 6250 1230 ÷ 5600 1320 ÷ 5800 1300 ÷ 5800
rpm
Frequency
55.5 ÷ 246.7
55 ÷ 208.3
61.5 ÷ 280
66 ÷ 290
65 ÷ 290
hz
tHeRmal unit iGnition
Now, to switch on the thermal unit:
- Make sure that the jumper or TA between terminals 7 and 8 is present
(and sending an ignition request to the boiler). if these conditions are
not present, the boiler does not work.
manual test function
This procedure allows forcing a Ch cycle, with adjustable output, lasting
no longer than 15 minutes.
7
8
7
8
Ambient
Thermostat
230Vac
43 44
43 44
Ambient
Thermostat
24Vac
Key to press
Description
Display
F
A
to view the MENU screen
to enter the TECHNiCAL MENU that requires a
PASSWORD
data
Ext.temp.
7
o
C
69
o
0.0
OFF OFF
ora
MENU
USER
TECHNICIAN
A
a
A
maui KR 115