- 37
-
INST
ALLA
TION
tecHnical
menu
Keys
sub-menu
Keys
sub-menu
Keys
lines
Keys
Factory
value
Range
5. usER sETTINGs
C
1.Ch
C
1.Temperature setting
range
C
1.Temperature setting
range
C
75°C
20 ÷ 90°C
D
B
D
2.External switch-off
temperature
C
OFF
OFF /
7 ÷ 25°C
D
2.ECO setpoint reduction
C
--->
--->
50°C
0 ÷ 50°C
D
3.Timer setting
C
1.Enable/Disable local
timer
C
Disabled
Enabled /
Disabled
D
2.Timer setting
C
Monday
days of the week
D
2.DHW
C
1.Temperature setting
range
C
--->
--->
80°C
30 ÷ 90°C
D
2.ECO setpoint reduction
C
--->
--->
20°C
0 ÷ 50°C
D
3.Timer setting
C
1.Enable/Disable local
timer
C
Disabled
Enabled /
Disabled
D
2.Timer setting
C
Monday
days of the week
D
3.Holiday
C
1.CH temperature
C
--->
--->
20°C
20 ÷ 90°C
D
2.DHW temperature
C
--->
--->
30°C
30 ÷ 90°C
6.CAsCADE
C
1.Cascade set
C
1.Cascade switch delay
C
--->
--->
60s
0÷255 s
D
B
D
2.Cascade min power
C
--->
--->
18%
0÷100%
D
3. Single burner power
C
--->
--->
115kW
0÷2550kW
D
4.Boiler for DHW
C
--->
--->
0
0÷6
D
5.Pi loop period
C
--->
--->
5s
1÷15 s
D
6.Burner waterflow delay
C
--->
--->
30s
0÷255 s
D
7. Different boiler size
C
--->
--->
Disabled
Enabled /
Disabled
D
8.Cascade pump speed
max
C
--->
--->
100%
15÷100%
D
9.Cascade pump speed
min
C
--->
--->
30%
15÷100%
D
2.Cascade info
C
--->
--->
--->
--->
Display only
D
3.Cascade autodetect
C
--->
--->
--->
--->
-----
-----