AST 14 C 255/00
P59
Type of temperature visualisation on
display
0 ÷ 7
0
0 = flow temperature
1 = amb. probe temp. 1
2 = amb. probe temp. 2
3 = external temperature
4
= water heater temp.
5 = solar collector temp.
6 = solar valve temp.
7 = solar valve temp. from
supplementary board
P60
Number of supplementary boards
connected to the mother board (zone +
solar)
0 ÷ 4
0
Max. 4 boards, three zone
boards and a solar card
P61
Association of remote control, thermostat
and ambient probe for the control of zone1
and zone2
00 ÷ 07
00
00 = remote control
zone2; Ta2 zone1;
01 = Ta1 zone2; Ta2
zone1;
02 = Ta2 zone2; remote
control zone1;
03 = SA1 zone1; Ta2
zone2;
04 = SA1 zone1; SA2
zone2;
05 = remote control
zone1; SA2 zone2;
06 = zone1 not controlled;
SA2 zone2;
07 = Ta1 zone1; SA2
zone2;
P62
Selection of zone 2 curve
0 ÷ 3
(1=100)
0.6
It can be set only with
connected zone board.
Without external probe:
value < 1, reduced range
(low temperature)
P63
Zone 2 set-point selection (fictitious temp.)
5 ÷ 30 °C
20°C
It can be set only with
connected zone board.
Without external probe:
Fixed flow set-point
P66
Selection of zone 3 curve
0 ÷ 3
(1=100)
0.6
It can be set only with two
connected zone boards
Without external probe:
value < 1, reduced range
(low temperature)
P67
Zone 3 set-point selection (fictitious temp.)
5 ÷ 30 °C
20°C
It can be set only with two
connected zone boards
Without external probe:
Fixed flow set-point
P70
Selection of zone 4 curve
0 ÷ 3
(1=100)
0.6
It can be set only with
three connected zone
boards
Without external probe:
value < 1, reduced range
(low temperature)
P71
Zone 4 set-point selection (fictitious temp.)
5 ÷ 30 °C
20°C
It can be set only with
three connected zone
boards
Without external probe:
Fixed flow set-point
P74
Low temperature zone mixer valve
0 to 300 s
140 s
It can be set only with
connected zone board.