________________________________________________________________________________
95
AST 14 C 255/00
Boiler shut-down, picture
flashes:
Communication failure
between main board
and supplementary
boards
The main board does not
find all supplementary
boards or finds more than
the ones actually connected
Check parameter P60
value. It must
correspond to the
number of
supplementary
board(s) used
Boiler shut-down, picture
flashes:
Hydraulic configuration
not allowed
The main board does not
recognise the probes for
correct operation
Check the P3 board
configuration
parameter.
Boiler shut-down, picture
flashes:
Configuration error
between ambient
probe, remote control
or supplementary zone
board
The main board does not
recognise the settings
matched with the zones
Check the system
configuration
parameter values (P60
and P61).
Boiler shut-down, picture
flashes:
Ambient probe 1 (SA1)
fault
Disconnected or short-
circuited probe
Reconnect or replace it
Boiler shut-down, picture
flashes:
Ambient probe 2 (SA2)
fault
Disconnected or short-
circuited probe
Reconnect or replace it
Boiler shut-down, picture
flashes:
Pressure transducer
fault
Faulty transducer
Replace it
Disconnected transducer
Connect it
Boiler shut-down, picture
flashes:
Communication failure
with the interface board
Disconnected
communication cable
RS485
Check connections
Interface board or mother
board fault
Replace faulty board