PROGRAMMING – INVERTING THE INPUTS & OUTPUTS
63 INVERT ARMING INPUTS
The Part & Full armed inputs are +ve applied. This option allows you to program
the inputs as +ve removed.
Key 1 – changes Part set input
Key 2 – changes Full set input
If the LED is off = +ve applied
If the LED is on = +ve removed
Press the full set key to exit
64 INVERT ZONE 1 – 8 RELAYS
The relays are normally de-energised. One or more of the relays can be set to be
energised all the time.
Key 1 changes zone 1
Key 2 changes zone 2
Key 3 changes zone 3
Key 4 changes zone 4
Key 5 changes zone 5
Key 6 changes zone 6
Key 7 changes zone 7
Key 8 changes zone 8
The 8 zone LED’s indicate zones 1 to 8
If LED is off relay is normally de-energised
If LED is on relay is normally energised
Press the full set key to exit
65 INVERT OTHER OUTPUTS
The voltage outputs are internally tied high going to 0v when active. Each output
is programmable.
Key 1 changes Tamper relay (Z1 LED on = relay normally energised)
Key 2 changes Low Battery (Z2 LED on=-ve removed. off = -ve applied
Key 3 changes Supervisory fault (Z3 LED on = -ve removed. Off=-ve applied