MODBUS-REGISTERS: TOTAL
[d] 1052
[h] 0x041C
41053
clear total
password
1
R/W
uint16 000...999
Setting 000 disables the clear total password feature.
[d] 2146
[h] 0x0862
42147
contract hour
1
R/W
uint16 0...23 Hour
[d] 2208
[h] 0x08A0
42209
current day total
4
R
uint64 0.000 ... 99999999999
Representation: unit, decimals depending on variables 32,
33.
[d] 2216
[h] 0x08A8
42217
previous day
total
4
R
uint64 0.000 ... 99999999999
Representation: unit, decimals depending on variables 32,
33.
MODBUS-REGISTERS: FLOWRATE
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 48
[h] 0x0030
40049
unit
1
R/W
uint16 0=none
1=mL
2=L
3=m
3
4=US GAL
5=I GAL
6=CF
7=OilBBL
8=nL
9=nm
3
10=SCF
11=mg
12=g
13=kg
14=ton
15=lb
16=US
17=rev
18=P
[d] 49
[h] 0x0031
40050
time unit
1
R/W
uint16 0=/sec
1=/min
2=/hour
3=/day
[d] 50
[h] 0x0032
40051
decimals
1
R/W
uint16 0…3
[d] 51
[h] 0x0033
40052
K-factor
2
R/W
uint32 1…9999999
Representation: 0.000010…9999999 depending on variable
54: decimals K-factor
[d] 54
[h] 0x0036
40055
K-factor
decimals
1
R/W
uint16 0…6
[d] 55
[h] 0x0037
40056
number of
pulses
1
R/W
uint16 1…255
[d] 56
[h] 0x0038
40057
cut-off time
1
R/W
uint16 1…9999
Representation: 0.0001…9.999sec
MODBUS-REGISTERS: DISPLAY
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 64
[h] 0x040
40065
display function
1
R/W
uint16 0=total
1=flowrate
2=acc.total
[d] 2147
[h] 0x863
42148
day totals
1
R/W
uint16 0=hidden
1=operate
2=off
[d] 80
[h] 0x050
40081
LCD update
time
1
R/W
uint16 0=fast
1=1sec
2=3sec
3=15sec
4=30sec
5=off
[d] 67
[h] 0x043
40068
backlight
brightness
1
R/W
uint16 0=off
1=20%
2=40%
3=60%
4=80%
5=100%
[d] 58
[h] 0x03A
40059
bar graph
enable
1
R/W
uint16 0=disable
1=enable
[d] 59
[h] 0x03B
40060
bar graph range
2
R/W
uint32 0…9999999
Representation: unit, time, decimals depending on variables
48, 49, 50
MODBUS-REGISTERS: FLOWMETER
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 96
[h] 0x060
40097
flowmeter signal
1
R/W
uint16 0=NPN
1=NPN LP
2=reed
3=reed LP
4=PNP
5=PNP LP
6=Namur
7=coil hi
8=coil lo
9=act 8.2V
10=act 24V
[d] 1051
[h] 0x41B
41052
K-factor unit
type
1
R/W
uint16 0=hand
1=volumetric
2=mass