Equipment damage from electrical discharge
● Electro static discharge can inflict irreparable damage to electronics! Before installing cabling,
always first discharge yourself by touching a well-grounded object.
● Always install the unit according to the EMC guidelines (Electro Magnetic Compatibility) and
according to local requirements (e.g. in Canada, the Canadian Electrical Code, C22.1, Part 1
and in USA, the National Electrical Code, NFPA 70 and ANSI/ISA-RP 12).
Risk of short circuits and overheating
● Use only an effective screened cable for the input signal and ground it to terminal S1 (GND)
AND to the housing, or at the sensor itself, whichever is appropriate to the application. Be
careful not to create ground loops.
● Without a thermal separator, the process temperature shall not exceed the specified maximum
ambient temperature.
● If, due to internal dissipation, the housing temperature exceeds 70 °C / 158 °F, use suitable
cable and gland to withstand high temperatures.
6.4.2
GROUNDING OF THE ENCLOSURE
For Class 1 applications make sure to apply proper in- and external grounding to PE terminal, as
shown. PE terminal: stranded conductor 4 mm
2
, single conductor 6 mm
2
.
Fig. 28:
Grounding of enclosure
6.4.3
ELECTRICAL RATINGS
The following supply ratings apply for installed options of the E-Series (other options have negligible
influence on the ratings). Use these ratings to select the suitable power supply and overcurrent
protection.
Type
Input
Supply voltage
range
Maximum supply
current
Remark
PD-OR P6
24-27 VDC
110 mA
Type OR
PD-OT P2
9-27 VDC
75 mA
Not Type OR
PX-OT P2
9-27 VDC
50 mA
Not Type OR
AH
A1/A2
11-27 VDC
25 mA
Type AH is not suitable for Type OR
If a combination of inputs is used, use the maximum value mentioned!
The output relay (Type OR) is type SPST and has the following contact ratings:
Load type & voltage
Current
Resistive load at 30 VDC, 125 VAC or 250 VAC.
Max. 2 A
Inductive load (for pilot duty applications) at 30 VDC, 125 VAC or 250 VAC.