10. HEAT RADIATION DATA
When in use, all Fluidmesh gateway units and radio transceivers generate
heat as a by-product of electrical activity.
Heat radiated by a Fluidmesh device may be of concern in confined
locations such as server rooms (where the cumulative heat generated by
a collection of electrical and electronic devices may cause damage to
sensitive electronic components) and outdoor equipment enclosures (in
which electronic components may overheat if the enclosure is not properly
ventilated).
WARNING
The outer surfaces of some Fluidmesh units may become hot
during normal operation. Such units have a 'Hot Surfaces'
warning triangle on their outer enclosures.
During normal operation, do not touch or handle such unit
enclosures without personal protective equipment.
The following table shows nominal heat-radiation figures for all Fluidmesh
devices under idle conditions, and under full-load conditions.
All heat-radiation figures are given in British Thermal Units (BTU) per
hour.
Device
Fiber-
optic
module
installed
Idle @
115 Vac /
60 Hz
Idle @
230 Vac /
60 Hz
Full load
@ 115
Vac / 60
Hz
Full load
@ 230
Vac / 60
Hz
FM 1000
gateway
25.590
33.780
25.250
33.100
FM 10000
gateway
271.595
267.159
436.395
437.078
PONTE 50
6.479
6.138
19.778
19.437
1200 VOLO
6.479
6.138
19.778
19.437
All 3200-series
transceivers
10.230
10.230
24.552
24.552
3500 ENDO
9.889
9.889
26.939
26.939
4200 MOBI
10.230
10.230
24.552
24.552
4200 FIBER
No
12.617
12.617
26.939
26.939
Yes
15.004
15.004
29.326
28.985
4500 MOBI
9.889
9.889
26.939
26.939
4500 FIBER
No
9.889
9.889
26.598
26.257
Yes
12.958
12.958
29.326
29.326
4800 FIBER
No
23.529
23.529
47.399
47.058
Yes
27.280
26.939
51.832
50.468