CONNECTING OF ELECTRICAL INSTALLATION
G-N-150; G-W-150; G-W-150 2R; G-E-150; G-N-200; G-W-200; G-W-200 2R; G-E-200; G-N-250; G-W-250; G-E-250
To supply curtain with power connect it by connection box closest to unit side (or G-W / N / E-250, two electrical connections to the fans are
required). Protract cable by glands (PG9 or PG11) and connect wires according to scheme from box cover.
G-E-150; G-E-200; G-E-250
To activate the curtain fans, the 3N 400V / 50 Hz heating elements should be powered by connecting the cables to the box located between the
fan nozzles (through the PG29 gland). Then connect the start signal from the RX manifold to the connectors (L; N through the PG9 gland).
WARNING
1. The power connection should be made in accordance with the technical documentation. The device
installation should always be carried out in accordance with applicable local safety standards.
2. The cross-section and type of the cable and the protection should be selected by the designer. Always
make sure that disconnectors and circuit breakers are properly sized and disconnect all poles of the power
supply
3. Make sure that the connection of power supply and controllers to the ELIS G curtain is made in
accordance with the electrical specifications and the instructions included in the connection diagrams in
the technical documentation.
4. Before connecting the power supply, check that the mains voltage corresponds to the voltage on the
device's type plate.
5. Check the power connection before connecting the air curtain.
6. Starting the device without connecting the grounding wire is not allowed.
7. Protect the power cord against pulling out by clamping it in the stuffing boxes of the fans and the
junction box.
8. Tighten all connection cables in the block properly
9. In the event of a hazard due to unintentional reset of the thermal switch, this curtain (ELIS G E) should
not be powered by an external connecting device such as a time switch, or connected to a circuit that is
regularly switched off and switched on during use.
Glands
PG29 + PG9
Power step [kW]
ELiS G
A
B
A + B
E-150
4,5
9,0
13,5
E-200
7,0
13,5
20,5
E-250
10,5
14,5
24,5