14
14.
CONTROL - DRV ELIS + T-BOX
In the case of connecting the DRV ELIS control module with an T-BOX intelligent controller to the RX splitter, it should be done instead of the
TS controller and use the diagrams available in the documentation of the RX splitter. In such a case, connecting the curtains to the RX splitter is
adequate to that presented in chapters 10 to 13.
15.
CONTROLS - OPTIONAL ELEMENTS
SRQ3d 3/4” – Three-way valve 3/4” with actuator
Protection degree: IP20
Supply voltage: 230/50 Hz
Max. medium temperature: +93
o
C
Max. Operating pressure: 2,1 MPa
Kvs: 6,5 m
3
/h
Installation: on the supply of the water heat exchanger
Motor running time: 18 s
A – Return pipe water supply
AB – Valve water supply
B – Exchanger water supply
SRQ2d 3/4” – Two-way valve 3/4” with actuator
Protection degree: IP20
Supply voltage: 230/50 Hz
Max. medium temperature: +93oC
Max. Operating pressure: 2,1 MPa
Kvs: 6,5 m3/h
Installation: on the supply of the water heat exchanger
Motor running time: 18
TS – 3-step regulator with built-in thermostat
Temperature setting range: +10 … +30
o
C
Operating temperature range: 0 … +40
o
C
Protection degree: IP30
Contact load: inductive 5 A
Supply voltage: 230 V/50 Hz
FAN AUTO - fan operation depends on the temperature.
FAN CONT - continuous fan operation
HEAT - heating function
FAN - deactivate the thermostat for FAN CONT
COOL - reversal of the operation logic of the thermostat
DCm – mechanical door contact
Operating temperature range: -10 -+80
o
C
Protection degree: IP 66
Connectors: 1xNC i 1xNO
Max current:
resistive – 10 A
inductive – 3 A
Max Power load: 300 Vac lub 250 Vdc
T-box – touch screen controller
Temperature setting range: +5 … +45
o
C
Operating temperature range: 0 … +60
o
C
Protection degree: IP30
Supply voltage: 24 VDC
DRV ELIS – control module
Operating temperature range:: 0 … +60
o
C
Protection degree: IP54
Supply voltage: 230 V/50 Hz
DRV ELIS can be connected to ELIS G air curtain only via RX splitter
RX – signal splitter
Operating temperature range:: 0 … +40 oC
Protection degree: IP54
Supply voltage: 230 V/50 Hz
To one RX can be connected maximum of 3 G-N/W/E-150 or G-N/W/E-200 curtains or maximum
of 2 G-N/W/E-250