(877) 356-5463 | (p) 330-331-7331 | (f) 330-331-7172 | www.FLO-CORP.com | © 2018 FLO-CORP | REVA 0918
5
(877) 356-5463 | (p) 330-331-7331 | (f) 330-331-7172 | www.FLO-CORP.com | © 2018 FLO-CORP | REVA 0918
6
The ‘Digitize’ function is an automatic setup routine to create a digital map of false echoes generated by
problems such as non-recommended mounting.
The function should be performed after physical installation to the application.
During the process the unit will prompt a measured distance (this must be either the material level if material
is touching the probe, or end of probe of the vessel is empty. For Interface model type it must be the Upper
Layer). The distance is adjustable if the displayed distance is not correct.
Ensure the value is not greater than the distance to the material level.
For best results follow this routine:
1) Ensure the unit is mounted according to mounting specifications and requirements.
2) Ensure the material to be measured is in contact with the actively measured part of the probe.
3) Select Dielectric pre-set value of most similar to material to be measured. For Interface model type it must
be the Upper Layer).
4) Run Digitize routine. Confirm displayed distance is either material level.
FAIL MODE
Set Failsafe reading
3.80mA
>20.20mA
LastKnown
4mA
20.00mA
>21.50mA
FAIL TIME
Set time delay for FailSafe condition (in seconds)
Adjustable
DIGITIZE
The ‘Digitize’ function is an automatic setup routine used to
eliminate false reflections. See ‘Digitze Function’ for further
information.
•
No
•
Yes
•
Disable
DIGITIZE FUNCTION
ADVANCED MENU
PARAMETER
DESCRIPTION
OPTIONS
COMMS
Adjust communication protocol settings. The default ID is 0,
and the default baud rate is 1200
•
Device ID
•
Baud Rate
SENSITIVITY
Manual adjustment of Sensitivity. Dieletric selection
automatically sets this value to defaults based on the Dieletric
selection. Sensitivity is the primary adjustment for the unit’s
ability to detect media. A higher value is used for lower Dk
materials or more difficult applications
•
0-100
BLANKING
Blanking is a non-measurable zone. This can be increased to
‘Blank’ out high level false echoes caused by mounting
Adjustable
<150mm
(6”) is not
recommended
Содержание TRACER 1000 3G LTT1-3G
Страница 15: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 15 ...
Страница 18: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 18 ...
Страница 20: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 20 ...
Страница 21: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 21 ...
Страница 22: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 22 ...
Страница 23: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 23 ...
Страница 24: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 24 ...
Страница 25: ... 877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2018 FLO CORP REVA 0918 25 ...